Nortec Industries GS Series Figure #7, Side Wall Venting Application Using BH Type Only, ft Min

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 12
Image 12
Figure #7

Figure #7

Vertical Venting Application Using B or BH Venting

UL Listed Cap

Required

Flashing

B or BH type vent using double wall ventFigure # 8 with double wall connectors is required. Reference local and/or national codes before installation of the vent.

Horizontal run

 

4" minimum air

1/4"rise per ft

 

space required

Exhaust venting

Condensate tee

outlet

required

 

 

 

 

 

B type double wall vent with

Steam Outlet

Trap

double wall connectors required

2 FT Min

for category I appliances.

 

 

3” Min.

Limitations on horizontal

 

 

distance when venting with B

 

 

vent

 

Condensate tee and

BH type double wall vent with

 

double wall connectors required

 

trap must be installed.

 

and all joints are to be air and

 

Take the condensate to

 

water tight. BH vent is a category

 

a floor drain or a

 

III appliances

 

condensate pump.

 

 

Figure # 8

Side Wall Venting Application Using BH Type Only

Wall Side Wall Venting Application Using BH Type Only

BH type vent using double wall vent with all joints being air and water tight. Reference local and/ or national codes before installing vent

Exhaust venting outlet

Wall Hangers Straps

2 ft Min. Nortec vent terminal

Condensate

Tee

Trap

2 ft Min.

Steam Outlet

3” Min.

3” Min. Condensate tee and trap must be installed. Take the condensate to a floor drain or a condensate pump.

BH type double wall vent with double wall connectors is required for category III appliances

Note: These are guidelines only, follow the local and/or national codes in your respective area.

- 8 -

Page 12
Image 12
Nortec Industries GS Series manual Figure #7, Side Wall Venting Application Using BH Type Only, ft Min, 3” Min