SCREEN 4:
SERVICE INTERVAL
XXX HOURS
REMAINING XXX HOURS
START DATE: MM:DD:YY
Service interval:
This field displays the user (or factory default) setting for the humidifiers service reminder in steam hours.
Remaining:
This field displays the amount of time (steam hours) remaining before the next service is to be performed.
Start Date:
This field displays the date this service interval began.
SCREEN 5:
SECURITY LOOP [0/1]
SAFETY SENSORS [0/1]
TANK SENSORS [0/1]
Security loop:
This field displays the status of the security loop (terminals 1 and 2 on LV terminal strip). If it is open the display will indicate “O”, if it is closed the display will indicate “I”.
Safety sensors:
This field displays the status of the safety sensors* input. If it is open the display will indicate “0”, if it is closed the display will indicate “1”.
*There are two safety sensors on the GSTC. One for tank over temperature and one for stack over temperature. Both sensors are wired in series.
Tank sensor
This field displays the status of the tank sensor input. If it is open the display will indicate “0”, if it is
closed the display will indicate “1”. Closed indicates that the tank temperature is above 160ºF (70ºC).
This input is used for the “keep warm” feature and for activating the fill valve during blowdown cycles.
SCREEN 6:
3 DAY DRAIN | 1 |
KEEP WARM | 0 |
BLOWDOWN RATE | XX% |
FT BLOWDOWN | 1 |
3 day drain
This field indicates if the feature has been selected (0 = no, 1 = yes).
Keep warm
This field indicates if the feature has been selected (0 = no, 1 = yes).
Blowdown rate:
This field displays the selected blowdown rate.
Full tank blowdown
This field indicates if the feature has been selected (0 = no, 1 = yes).
- 51 -