Nortec Industries GS Series manual Day Drain, Keep Warm, Maintenance Gsp, Analog Channel

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 43
Image 43

3 DAY DRAIN

3 DAY DRAIN FUNCTION

SW3/7

 

 

Function Disabled

OFF

 

 

Function Enabled (Factory set)

ON

 

 

 

 

KEEP WARM

3 DAY DRAIN FUNCTION

SW5/7

 

 

Function Enabled

ON

 

 

Function Disabled (Factory set) - 3 day drain

OFF

 

 

 

 

MAINTENANCE (GSP)

MAINTENANCE INTERVAL (GSP)

SW3/8

 

 

500 hour (Factory set)

OFF

 

 

1000 hour

ON

 

 

 

 

ANALOG CHANNEL 1

Input Range

SW1/1

SW4/1

SW 4/2

 

 

 

 

0-10V input

OFF

OFF

OFF

 

 

 

 

0-5V input

OFF

ON

OFF

 

 

 

 

2-10V input

OFF

OFF

ON

 

 

 

 

1-5V input

OFF

ON

ON

 

 

 

 

0-20mA input

ON

OFF

OFF

 

 

 

 

0-10mA input

ON

ON

OFF

 

 

 

 

4-20mA input

ON

OFF

ON

 

 

 

 

2-10mA input

ON

ON

ON

 

 

 

 

 

 

 

 

ANALOG CHANNEL 2

Input Range

SW1/2

SW4/3

SW 4/4

 

 

 

 

0-10V input

OFF

OFF

OFF

 

 

 

 

0-5V input

OFF

ON

OFF

 

 

 

 

2-10V input

OFF

OFF

ON

 

 

 

 

1-5V input

OFF

ON

ON

 

 

 

 

0-20mA input

ON

OFF

OFF

 

 

 

 

0-10mA input

ON

ON

OFF

 

 

 

 

4-20mA input

ON

OFF

ON

 

 

 

 

2-10mA input

ON

ON

ON

 

 

 

 

 

 

 

 