Y = total number of recorded services (up to 10 maximum).
STEAM HOURS XXX (DATE/TIME)
This field displays the steam hours and the date and time when the specific service (X) was performed.
SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY
TANK DRAIN TANK
SHORT CYCLE DELAY
FAULT HISTORY X/Y
(TYPE OF FAULT)
(DATE/TIME)
Fault history
In this area the customer can view the history of recorded faults for the humidifier.
FAULT HISTORY X/Y
The fault history stores the last 54 system faults.
X = fault occurrence, where 1 is the most recent.
Y = total number of recorded faults (up to 54 maximum).
(type of fault) and (date/time)
A description of the fault type is displayed along with a date and time stamp when the fault occurred.
SERVICE INTERVAL
SERVICE HISTORY
FAULT HISTORY TANK DRAIN
TANK
SHORT CYCLE DELAY
THIS WILL DRAIN CONTENTS OF TANK
THIS WILL DRAIN CONTENTS OF TANK
CONTINUE?
Tank Drain
The tank drain feature, when activated, will activate the drain valve for a fixed period of time (depending on unit size).
To drain the tank press enter when CONTINUE is selected. During the tank drain cycle the display will indicate the tank is draining and the amount of time remaining on the cycle. To interrupt the cycle the unit must be switched off then on. Must enter service password to activate this function.