Nortec Industries GS Series Input Channel, Time Proportioning, Blowdown Gsp, Maintenance Shutdown

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 44
Image 44

INPUT CHANNEL

DUAL CHANNEL FUNCTION

SW4/5

 

 

One Channel Input

OFF

 

 

Dual Channel Inputs

ON

 

 

 

 

TIME PROPORTIONING

TIME PROPORTIONING

SW4/7

 

 

Disabled (Factory set)

OFF

 

 

Enabled

ON

 

 

 

 

BLOWDOWN (GSP)

BLOWDOWN

SW5/1

SW 5/2

SW5/3

 

 

 

 

5%

ON

OFF

OFF

 

 

 

 

10%

OFF

ON

OFF

 

 

 

 

15%

ON

ON

OFF

 

 

 

 

20%

OFF

OFF

ON

 

 

 

 

25% (Factory set)

ON

OFF

ON

 

 

 

 

30%

OFF

ON

ON

 

 

 

 

35%

ON

ON

ON

 

 

 

 

 

 

 

 

MAINTENANCE SHUTDOWN

MAINTENANCE SHUTDOWN FUNCTION

SW5/4

 

 

Unit will shutdown 72 hours after service time expired, by gen-

OFF

erating an error.

 

 

 

Unit will display warning but continues to operate. (Factory set)

ON

 

 

 

 

FULL TANK BLOWDOWN

FULL TANK BLOWDOWN FUNCTION

SW5/8

 

 

Disabled

OFF

 

 

Enabled (Factory set)

ON

 

 

 

 

- 40 -

Page 44
Image 44
Nortec Industries GS Series Input Channel, Time Proportioning, Blowdown Gsp, Maintenance Shutdown, Full Tank Blowdown