INPUT CHANNEL
DUAL CHANNEL FUNCTION | SW4/5 |
|
|
One Channel Input | OFF |
|
|
Dual Channel Inputs | ON |
|
|
|
|
TIME PROPORTIONING
TIME PROPORTIONING | SW4/7 |
|
|
Disabled (Factory set) | OFF |
|
|
Enabled | ON |
|
|
|
|
BLOWDOWN (GSP)
BLOWDOWN | SW5/1 | SW 5/2 | SW5/3 |
|
|
|
|
5% | ON | OFF | OFF |
|
|
|
|
10% | OFF | ON | OFF |
|
|
|
|
15% | ON | ON | OFF |
|
|
|
|
20% | OFF | OFF | ON |
|
|
|
|
25% (Factory set) | ON | OFF | ON |
|
|
|
|
30% | OFF | ON | ON |
|
|
|
|
35% | ON | ON | ON |
|
|
|
|
|
|
|
|
MAINTENANCE SHUTDOWN
MAINTENANCE SHUTDOWN FUNCTION | SW5/4 |
|
|
Unit will shutdown 72 hours after service time expired, by gen- | OFF |
erating an error. |
|
|
|
Unit will display warning but continues to operate. (Factory set) | ON |
|
|
|
|
FULL TANK BLOWDOWN
FULL TANK BLOWDOWN FUNCTION | SW5/8 |
|
|
Disabled | OFF |
|
|
Enabled (Factory set) | ON |
|
|
|
|
- 40 -