Nortec Industries GS Series manual Mandatory Maintenance Schedule

Models: GS Series

1 78
Download 78 pages 6.36 Kb
Page 33
Image 33
MANDATORY MAINTENANCE SCHEDULE

- 2 9 -

MANDATORY MAINTENANCE SCHEDULE

 

30 DAYS

 

END OF

WHAT NEEDS TO BE DONE?

PARTS

after initial

MID

 

 

SEASON

REGULAR MAINTENANCE

PREVENTIVE MAINTENANCE

 

start-up

 

 

 

 

 

 

 

 

 

 

Hot Surface

 

 

X

- Check for continuity.

 

Ignitor

 

 

 

 

 

 

 

- Replace hot surface ignitor and flame

 

 

 

 

 

 

 

 

X

- Check that Flame Sensor is straight.

sensor with replacement kit.

Flame Sensor

 

 

 

 

 

 

- Clean sensor with fine steel wool.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Remove from the unit and clean with compressed

 

 

 

 

 

air from outside matting.

 

Gas Burner

 

 

X

 

 

 

 

NOTE: It is recommended to replace the burner

 

 

 

 

 

 

 

 

 

 

gasket each time a burner is removed.

 

 

 

 

 

 

 

Drain Lines

 

 

X

- Switch to drain and make sure water flows freely.

 

 

 

 

 

 

 

 

 

 

 

- Adjust blow down time when required. Check that

- Drill out tank nipples when required to

Tank

X

X

X

scale has not accumulated above 2".

ensure nipples are not blocked with scale.

 

 

 

 

 

 

 

 

 

 

 

 

- Clean tank when required.

- Clean tank.

 

 

 

 

 

 

Float Chamber

X

X

X

- Ensure floats move freely.

- Clean scale from float chamber and hose

connecting to hit.

 

 

 

 

 

 

 

 

 

 

 

Fill Lines

X

X

X

- Inspect for leaks.

 

 

 

 

 

 

 

Drain Lines

X

X

X

- Inspect for leaks at the drain pump, fill cup and

 

float chamber.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Inspect for leaks. Ensure terminal cap is clear and

 

Gas Venting

X

X

X

any condensation produced flows to condensate

 

 

 

 

 

traps. Flue temp should be between 350-400ºF.

 

 

 

 

 

 

 

Direct Vent

 

X

X

- Inspect for leaks. Ensure intake terminal is clear.

 

 

 

 

 

 

 

H/L Stack Sensor

X

X

X

- Visual check that sensor is intact, wired and

 

attached to the exhaust.

 

 

 

 

 

 

 

 

 

 

 

 

Page 33
Image 33
Nortec Industries GS Series manual Mandatory Maintenance Schedule