SYSTEM STATUS

SYSTEM STATUS

SCREEN 1:

STATUS: LOCKOUT

DEMAND CHANNEL 1 0%

DEMAND CHANNEL 2 0%

CAPACITY LIMIT

0%

Status:

Displays the present status of the system. Depending on system activity at the time, the field could display: lockout (security loop open), active (unit generating steam) or standby (security loop closed but no modulation demand signal).

Demand channel 1:

This field will display the modulation demand input on that channel.

Demand channel 2:

Field only visible if the unit is configured for dual modulation. This field will display the modulation demand input on that channel.

Capacity limit:

This field displays the user adjusted capacity limit set for the humidifier.

SCREEN 2:

SYSTEM DEMAND XXX%

BURNERS ACTIVE X/X

OUTPUT/BURNER XXXLB

TOTAL OUTPUT

XXXLB

System demand:

This field displays the total system demand as a percentage.

Burners active:

This field displays the number of active burners and the number of available burners.

Output/Burner:

This field will display the actual output of steam generated by each burner (kg/hr or lbs/hr).

Total output:

This field will display the total system steam output (kg/hr or lbs/hr).

SCREEN 3:

WATER LEVEL:

X

FILL VALVE

ON

DRAIN VALVE

OFF

DRAIN COOLING: SMART

Water level:

This field displays the present water level detected by the float system.

Fill valve:

This field displays status of fill valve, on, off, or pulsed.

Drain valve:

This field displays status of drain pump, on or off.

Drain cooling:

This field displays the user (or factory default) setting.

OFF: fill will not activate when drain is activated.

ON: fill will activate whenever the drain activates.

SMART: fill will activate only when drain water is

hot.