SYSTEM STATUS
SCREEN 1:
STATUS: LOCKOUT
DEMAND CHANNEL 1 0%
DEMAND CHANNEL 2 0%
CAPACITY LIMIT | 0% |
Status:
Displays the present status of the system. Depending on system activity at the time, the field could display: lockout (security loop open), active (unit generating steam) or standby (security loop closed but no modulation demand signal).
Demand channel 1:
This field will display the modulation demand input on that channel.
Demand channel 2:
Field only visible if the unit is configured for dual modulation. This field will display the modulation demand input on that channel.
Capacity limit:
This field displays the user adjusted capacity limit set for the humidifier.
SCREEN 2:
SYSTEM DEMAND XXX%
BURNERS ACTIVE X/X
OUTPUT/BURNER XXXLB
TOTAL OUTPUT | XXXLB |
System demand:
This field displays the total system demand as a percentage.
Burners active:
This field displays the number of active burners and the number of available burners.
Output/Burner:
This field will display the actual output of steam generated by each burner (kg/hr or lbs/hr).
Total output:
This field will display the total system steam output (kg/hr or lbs/hr).
SCREEN 3:
WATER LEVEL: | X |
FILL VALVE | ON |
DRAIN VALVE | OFF |
DRAIN COOLING: SMART
Water level:
This field displays the present water level detected by the float system.
Fill valve:
This field displays status of fill valve, on, off, or pulsed.
Drain valve:
This field displays status of drain pump, on or off.
Drain cooling:
This field displays the user (or factory default) setting.
OFF: fill will not activate when drain is activated.
ON: fill will activate whenever the drain activates.
SMART: fill will activate only when drain water is
hot.
- 50 -