D9412GV3/D7412GV3 Program Entry Guide 2.0 Panel and Area Wide Parameters

EN 80

When sharing one relay to reset sensors in two or more areas, you must program the following. Failure to do so causes TROUBLE PT ### for all point types programmed as P## Resettable.

CC # Scope must include all areas that share the relay.

L## Reset Sensors authority must be assigned to the passcode that activates the COMMAND 47 or Reset Sensor function.

A# Verify Time must be the same number of seconds for all areas that share the relay.

To meet UL 864 requirements, set A# Reset Sensors to a value other than 0.

A# Fail to Close

A# Watch Mode

Default: 0

Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C

This relay activates when a Controlled point programmed for P## Watch Point is faulted in the specified area while the area is in Watch Mode and the point is not armed. It remains active for 2 sec after each point is faulted.

A# Area Armed

Default: 0

Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C

This relay activates when the specified area becomes Master Armed. The exit delay must expire before the relay activates. The relay remains active until the area disarms. It does not deactivate during the entry delay time.

Default: 0

Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C

This relay activates when the Closing Window expires for the specified area. It remains active until midnight, another Closing Window starts, or the control panel resets, whichever occurs first. When Perimeter Relay (refer to page 139) is set to Yes, the A# Fail to Close prompt becomes A# Perimeter Relay.

A# Force Armed

Default: 0

Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C

This relay activates when this area is Force Armed. It remains active until the area disarms or the control panel resets.

If Force Bypassing is required during Perimeter Arming, this relay does not activate.

If multiple areas use the same relay, the relay activates when all areas are armed. It deactivates when the first area disarms.

The A# Area Armed relay function can provide visual feedback at a key switch station. Attach a LED to the output of a D8129 Module programmed for this function.

A# Area Fault

Default: 0

Selection: 0, 1 to 128 for D9412GV3, 1 to 64 for D7412GV3, A, B, or C

Activates whenever a controlled (P## Type 1, 2, 3 only) Perimeter or Interior point is faulted. The relay remains active until all Perimeter and Interior points in the area are normal.

Keyswitch area armed status with LEDs: Use a D8129 Module and connect an LED to indicate that the area is not ready to arm.

Bosch Security Systems, Inc. 10/11 F01U170807-02