Bosch Appliances D9412GV3 Passcode Length, Swinger Count, Remote Warning, Crystal Time Adjust

Models: D9412GV3

1 154
Download 154 pages 49.97 Kb
Page 138
Image 138

D9412GV3/D7412GV3 Program Entry Guide 5.0 AUXPARM

EN 138

For SIA CP-01 Compliance:

Abort Window is a required parameter.

To meet UL requirements, the combined Entry Delay time and Abort Window time must not exceed 60 sec. For Entry Delay time programming information, refer to P## Entry Delay in the Point Responses section of your control panel’s program entry guide.

UL note: Maximum settings for residential use:

Exit Delay – 120 sec Entry Delay = 45 sec bell

Off-Premise Transmission = 60 sec Maximum settings for commercial use:

Exit Delay – 120 sec no line security Entry Delay = 60 sec bell Off-Premise Transmission = 60 sec

The system must use both the bell and off-premise transmission.

Passcode Length

Default: 0

Selection: 0, 3, 4, 5, or 6

0Sets a variable length for user passcodes, allowing for backward compatibility

3, 4, 5,

Sets a fixed length to all user

or 6

passcodes.

During entry delay, the code is accepted when the last digit is pressed to disarm the area.

For SIA CP-01 Compliance:

Passcode Length must be set to 3, 4, 5, or 6.

Swinger Count

Default:

1

Selection:

1, 2, 3, or 4

1, 2

Number of fault or trouble bypasses

 

allowed per hour for SIA CP-01

 

compliance.

3Optional fault count

4Value used for backward compatibility with previous control panel operation.

When a point has P# Swinger Bypass set to Yes, the value set in Swinger Count determines the number of times the point is faulted erroneously within an hour before it is automatically bypassed.

For SIA CP-01 Compliance:

P## Swinger Bypass can be Yes or No.

If P## Swinger Bypass is Yes, Swinger Count must be 1 or 2.

Remote Warning

 

Default:

 

 

Yes

 

Selection:

 

 

 

 

 

 

Yes or No

 

Yes

The system uses the Alarm Bell

 

 

 

 

output to annunciate the arming and

 

 

 

 

disarming of an area through remote

 

 

 

 

software, or a remote arming device

 

 

 

 

such as a key switch or key fob.

 

 

 

 

No

No remote warning occurs to

 

 

 

 

annunciate the arming and disarming

 

 

 

 

of an area through remote software,

 

 

 

 

or a remote arming device such as a

 

 

 

 

key switch or key fob.

 

 

 

 

 

Upon remote arming, the output pulses on for 2 sec. Upon remote disarming, the output pulses on, off, on, off for 2 sec each.

For SIA CP-01 Compliance

Remote Warning must be set to Yes.

Crystal Time Adjust

Default:

No

Selection:

Yes or No

Yes

Set the clock time control on the

 

control panel to the on-board crystal

 

frequency.

 

 

No

Do not set the clock time control on

 

the control panel to the on-board

 

crystal frequency.

 

 

When set to Yes, the control panel switches its clock time control from the traditional AC frequency to the on-board crystal frequency.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Page 138
Image 138
Bosch Appliances D9412GV3 manual Passcode Length, Swinger Count, Remote Warning, Crystal Time Adjust