DS7400XiV4-EXP User Guide 9.0 Error Displays

EN 25

9.0 Error Displays

You can read error displays only when the control panel is disarmed. Some control panel errors, such as battery trouble and any RF troubles, cause the keypad sounders to beep every 10 seconds.

You can silence the keypad sounders for 4 hours by entering [PIN][Off].

The sounders continue to sound until the problem is fixed.

Clear the error display as advised by your installing company, or if you are certain the problem is remedied.

Table 23: Error Displays

 

 

 

 

 

 

 

Error/Warning Messages

 

 

 

LED Keypad

 

Text Keypad

 

Meaning

 

 

 

 

 

 

 

 

 

 

Power Light

 

Control Trouble

 

There is an Error Message. To display the message, enter [PIN][#][8][7].

 

(green) flashing

 

Enter [#][8][7]

 

 

 

LED 1 on

 

AC Power Failure

 

There is a power failure and the control panel is operating on backup battery power.

 

 

 

 

 

 

 

LED 2 on

 

Battery Trouble *

 

If there was a power failure, wait at least two hours for the battery to recharge, then

 

 

 

 

 

enter [PIN][System Reset] to perform a battery test.

 

LED 3 on

 

Communicator Err **

 

The control panel failed to communicate with the central station.

 

 

 

 

 

 

 

LED 4 on

 

System Fault

 

Internal error in the control circuitry or optional circuitry. Refer to Section 9.1

 

 

 

 

 

System Faults.

 

LED 5 on

 

Keypad Fault

 

One of the keypads is not responding to the control panel.

 

 

 

 

 

 

 

LED 6 on

 

Keypad Tamper

 

One of the keypad housings was opened.

 

LED 7 on

 

Multiplex Bus

 

The multiplex bus is defective or is shorted.

 

 

 

 

 

 

 

LED 8 on

 

Aux. Power Fault

 

The auxiliary power is shorted.

 

 

 

Zone Trouble

 

One of the zones is not responding to the control panel. This might also be

 

 

 

 

 

displayed during power-up; if this occurs, ignore the message.

 

 

 

RF

 

Indicates a problem with an RF (wireless) zone.

 

 

 

Dirty Chamber

 

One of the multiplex smoke detectors failed the sensitivity test and might require

 

 

 

 

 

cleaning or replacement. Clear the keypad beep by entering [PIN][Off]

 

 

 

 

 

 

*The Battery Trouble message is cleared only by the [System Reset] command or another Automatic Battery Test, even after the problem is remedied.

**The Communicator Error message is cleared only by the [System Reset] command or the next successful Automatic System Off Normal report, even after the problem is remedied.

Bosch Security Systems 6/05 4998154961B

Page 25
Image 25
Bosch Appliances DS7400XIV4-EXP manual Error Displays, System Faults