10.4Fire Walk Test

DS7400XiV4-EXP User Guide 10.0

Testing Your System

 

 

EN 29

10.4Fire Walk Test

This test confirms that smoke detectors report alarms to the keypads. The Fire Walk Test tests all fire zones, including verified fire and waterflow.

This test requires you to manually alarm each zone.

If programmed, a Fire Walt Test report is sent to the central station at the start of a Fire Walk Test. Fire alarm reports are not sent to the central station during the Fire Walk Test. A Fire Walk Test restoral is sent upon completion of the Fire Walk Test.

The Fire Walk Test runs for 20 minutes once it is started. The test time is extended to 20 minutes every time you test another zone.

When you test a fire zone, any output programmed to follow that zone is activated for 5 seconds.

Table 28: Fire Walk Test

 

 

 

 

Type of Test

Command Sequence

What Happens

What To Do

 

 

 

 

Fire Walk Test

[PIN][#][9][1]

• “Fire Test” is displayed followed by the number

• Test each zone as

 

 

of any zones that are untested. *

instructed by your

 

 

• The LEDs of any untested zones flash. **

installing company.

 

 

• “Fire Testing” is displayed followed by the

• Exit the Fire Walk Test

 

 

number of the zone currently being tested. *

using [PIN][#].

 

 

• The LED for the zone currently being tested

 

 

 

turns on steady. **

 

 

 

• As each zone is tested, the “Fire Test” message

 

 

 

appears followed by the remaining untested

 

 

 

zones. *

 

 

 

• As each zone is tested, its LED turns off. **

 

*Text keypad only ** LED keypad only

A Fire Walk Test prevents the system from sending any Fire Reports during the test.