Bradford-White Corp U4TW40T*FRN Troubleshooting, Page, LED Status, Control Status, Probable Cause

Models: U4TW60T*FRN U4TW40T*FRN U4TW50T*FRN

1 52
Download 52 pages 25.44 Kb
Page 19
Image 19
Manual background

 

 

 

 

 

Troubleshooting

 

 

 

 

 

 

 

 

 

LED Status

Control Status

 

Probable Cause

 

Service Procedure

 

 

 

 

 

 

 

 

 

 

 

 

1.

Damage to thermal well wires

 

 

 

 

 

 

2.

Thermal well sensor resistance

 

 

 

 

Eight flashes,

Thermal well sensor

out of range

 

 

 

 

three flashes,

damaged or un-

3.

Replace thermal well

 

See Thermal Well Testing on

 

 

plugged or gas con-

4.

Verify control is not wet or

 

 

 

three second

trol electronics fault

physically damaged

 

page 34

 

 

pause

detected

5.

Reset control on/off switch

 

 

 

 

 

 

 

 

 

 

 

6.

Replace gas control if 8-3 error

 

 

 

 

 

 

persists

 

 

 

 

 

 

 

 

 

 

 

 

Eight flashes,

 

1.

Verify control is not wet or

 

1. Replace gas control if wet

 

 

 

physically damaged

 

 

 

four flashes,

Gas control fault

 

or physically damaged

 

 

2.

Reset control on/off switch

 

 

 

three second

detected

 

2. Cycle power

 

 

3.

Replace gas control if 8-4 error

 

 

 

pause

 

 

3. Replace gas control

 

 

 

 

persists

 

 

 

 

 

 

 

 

 

 

 

Page 19

19

Page 19
Image 19
Bradford-White Corp U4TW40T*FRN Troubleshooting, Page, LED Status, Control Status, Probable Cause, Service Procedure