Bradford-White Corp U4TW50T*FRN Vent Tables, Specifications, Page, Gallon 50 Gallon 60 Gallon

Models: U4TW60T*FRN U4TW40T*FRN U4TW50T*FRN

1 52
Download 52 pages 25.44 Kb
Page 9
Image 9
Vent Tables

Specifications

Vent Tables

Venting Specifications for:

40Gallon

50Gallon

60Gallon

2” Diameter (5.1 cm) PVC Vent Connector Lengths

Terminating

# of Elbows

Maximum Straight

Minimum Straight

Length ft (m)

Length ft (m)

 

 

 

 

 

 

Through the Wall

1

45 (13.7)

2 (0.6)

 

 

 

 

Through the Wall

2

40 (12.2)

2 (0.6)

 

 

 

 

Through the Wall

3

35 (10.7)

2 (0.6)

 

 

 

 

Through the Wall

4

30 (9.2)

2 (0.6)

 

 

 

 

 

 

 

 

Through the Roof

0

50 (15.2)

7 (2.1)

 

 

 

 

Through the Roof

1

45 (13.7)

7 (2.1)

 

 

 

 

Through the Roof

2

40 (12.2)

7 (2.1)

 

 

 

 

Through the Roof

3

35 (10.7)

7 (2.1)

 

 

 

 

Through the Roof

4

30 (9.2)

7 (2.1)

 

 

 

 

3” Diameter (7.6 cm) PVC Vent Connector Lengths

Terminating

# of Elbows

Maximum Straight

Minimum Straight

Length ft (m)

Length ft (m)

 

 

 

 

 

 

Through the Wall

1

115 (35.0)

10 (3.1)

 

 

 

 

Through the Wall

2

110 (33.5)

10 (3.1)

 

 

 

 

Through the Wall

3

105 (32.0)

10 (3.1)

 

 

 

 

Through the Wall

4

100 (30.5)

10 (3.1)

 

 

 

 

Through the Wall

5

95 (29.0)

10 (3.1)

 

 

 

 

 

 

 

 

Through the Roof

0

120 (36.6)

15 (4.6)

 

 

 

 

Through the Roof

1

115 (35.0)

15 (4.6)

 

 

 

 

Through the Roof

2

110 (33.5)

15 (4.6)

 

 

 

 

Through the Roof

3

105 (32.0)

15 (4.6)

 

 

 

 

Through the Roof

4

100 (30.5)

15 (4.6)

 

 

 

 