46 Brocade ICX 6650 Hardware Installation Guide
53-1002599-01
Environmental considerations
A
Environmental considerations
Table 4 lists the acceptable environmental ranges for both operating and nonoperating (such as
during transportation or storage) conditions.
Cooling system and fans
Fans cool the CPU, main memory, and voltage regulators. For Brocade ICX 6650 switches, the fans
use either:
An exhaust airflow which moves air from front to back. See Figure19. Devices with exhaust
airflow are labeled with a green arrow with “E.” See Figure20.
An intake airflow which moves air from back to front. See Figure21. Devices with intake airflow
are labeled with an orange arrow with “I.” See Figure22.
CAUTION
Be sure that the airflow direction of the power supply unit matches that of the installed fan tray.
The power supplies and fan trays are clearly labeled with either a green arrow with an “E” for
exhaust, or an orange arrow with an “I” for intake.
TABLE 4 Environmental requirements
Condition Acceptable during operation Acceptable during non-operation
Ambient
Temper ature
0º to 40ºC (32º to 104ºF) -25º to 70ºC (-23º to 158ºF)
Humidity 10% to 95% RH non-condensing, at
40ºC (104ºF)
5% to 80% RH non-condensing, at 70ºC
(158ºF)
Altitude 0 to 3 km (9,842 feet) above sea level 0 to 12 km (39,370 feet) above sea level
Shock 20 G, 6 ms, half-sine wave 33 G, 11 ms, half-sine wave, 3/eg Axis
Vibration 0.5 G sine, 0.4 gms random, 5-500 Hz 2.0 G sine, 1.1 gms random, 5-500 Hz
Airflow Maximum - 90.1 cmh (53 cfm)
Nominal - 59.5 cmh (35 cfm)
N/A
Heat
dissipation
478 BTU/hr N/A
Operating
noise
46.7 dB N/A