Bryant 580F Viii. — Adjust Factory-Installedoptions, A. Manual Outdoor-AirDamper

Models: 580F

1 80
Download 80 pages 29.14 Kb
Page 17
Image 17
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS

VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS

A. Manual Outdoor-Air Damper

The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.

Assembly:

1.Determine quantity of ventilation required for build- ing. Record amount for use in Step 8.

2.Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove the filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 12.

3.Separate hood and screen from basepan by removing the screws and brackets securing them. Save all screws and discard brackets.

4.Replace outdoor air opening panel with screws saved from Step 2.

5.Place hood on front of outdoor-air opening panel. See Fig. 13 for hood details. Secure top of hood with the 6 screws removed in Step 3. See Fig. 14.

6.Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.

7.Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.

8.Adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position determined by Fig. 15. Tighten screws.

9.Remove and save screws currently on sides of hood. Insert screens. Secure screens to hood using the screws. See Fig. 14.

10.Replace filter access panel. Ensure filter access panel slides along the tracks and is securely engaged.

OUTDOOR

AIR OPENING

PANEL

Fig. 13 — Outdoor-Air Hood Details

HOOD

NOT

SHOWN)

3 SCREWS

Fig. 14 — Optional Manual Outdoor-Air Damper

with Hood Attached

(SIDE)

Fig. 12 — Damper Panel with Manual

Outdoor-Air Damper Installed

Fig. 15 — Outdoor-Air Damper Position Setting

17

Page 17
Image 17
Bryant 580F Viii. — Adjust Factory-Installedoptions, A. Manual Outdoor-AirDamper, Outdoor-AirHood Details