The user can read the value of the sensor using the Read mode, described in the EconoMi$er+ Controller section.
Mount the return air temperature sensor on the EconoMi$er+, through
The return air temperature (RAT) sensor is provided with a
This 10K thermistor is used to measure the return air temperature vs. resistance curve, per Table 5. The range of temperature measurement is between 0° and 158 F. See Table 6 for resolution.
K. Outdoor Air Humidity Sensor
The EconoMi$er+ controller accepts input from the accessory outdoor air humidity sensor in addition to the outdoor air tem- perature sensor shipped with the EconoMi$er+. By using both sensors, the total enthalpy of the outside air is calculated.
Mount the
The outdoor enthalpy changeover curve is set at the EconoMi$er+ controller. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
L. Indoor Air Humidity Sensor
For differential enthalpy sensing, the EconoMi$er+ control- ler uses the standard outdoor air temperature sensor, the outdoor air humidity sensor, and the optional indoor air humidity sensor, an optional return air temperature sensor (RAT). The
The controller selects the lower enthalpy air (return or out- door) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er+ control- ler opens the damper to bring in outdoor air for free cooling.
Mount the
The outdoor enthalpy changeover curve is set with at the EconoMi$er+ controller. The selectable curves are A, B, C, and D. The factory default is curve “A.” See Fig. 29. See Fig. 30 for Sensor Curve vs. Humidity.
CO2 SENSOR MAX RANGE SETTING
| 6000 |
|
|
|
|
|
|
(ppm) | 5000 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
CONFIGURATION | 4000 |
|
|
|
|
| 800 ppm |
|
|
|
|
|
| ||
3000 |
|
|
|
|
| 900 ppm | |
|
|
|
|
| 1000 ppm | ||
|
|
|
|
|
| ||
2000 |
|
|
|
|
| 1100 ppm | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
RANGE | 1000 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 0 |
|
|
|
|
|
|
| 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| DAMPER VOLTAGE FOR MAX VENTILATION RATE |
Fig. 26 — Indoor Air Quality Voltage Setting
ECONOMI$ER+ CONTROLLER |
HOOD |
ACTUATOR |
RETURN AIR |
TEMP SENSOR |
(HIDDEN) |
GROMMET |
CURB
INDOOR AIR
HUMIDITY SENSOR
VERTICAL ECONOMI$ER+ (3 TO 12 1/2 TON UNITS)
(SIDE VIEW)