Bryant 580F 27, CO2 Sensor* Standard Settings, Ix. — Adjust Evaporator-Fanspeed, for Sizes

Models: 580F

1 80
Download 80 pages 29.14 Kb
Page 27
Image 27
Table 7 — CO2 Sensor* Standard Settings

Table 7 — CO2 Sensor* Standard Settings

 

 

 

VENTILATION

ANALOG

CO2 CONTROL

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

RELAY SETPOINT

HYSTERESIS

 

 

 

(cfm/Person)

OUTPUT

RANGE (ppm)

(ppm)

(ppm)

 

 

 

 

 

1

Interface with Standard

Proportional

Any

4-20 mA

0-2000

1000

50

2

Proportional

Any

7-20 mA

0-2000

1000

50

Building Control System

3

Exponential

Any

4-20 mA

0-2000

1100

50

 

4

 

Proportional

15

4-20 mA

0-1100

1100

50

5

Economizer

Proportional

20

4-20 mA

0- 900

900

50

6

Exponential

15

4-20 mA

0-1100

1100

50

 

7

 

Exponential

20

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/ Loading Docks

Proportional

4-20 mA

0-2000

700

50

LEGEND

ppm — Parts Per Million

*Available sensor part numbers are listed in Table 4.

IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED

Adjust evaporator-fan speed to meet jobsite requirement.

Table 8 shows fan rpm at motor pulley settings and Table 9 shows motor efficiencies. Table 10 shows motor performance. Refer to Fan Performance Tables 11-30 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Tables 1A and 1B.

To change fan speed:

1.Shut off unit power supply and install lockout tag.

2.Loosen belt by loosening fan motor mounting plate nuts (see Fig. 33 and 34).

3.Loosen movable pulley flange setscrew (see Fig. 35).

4.Screw movable flange toward fixed flange to increase fan speed and away from fixed flange to decrease fan speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Tables 1A and 1B.

5.Set movable flange at nearest flat of pulley hub and tighten setscrew (see Tables 1A and 1B for speed change for each full turn of pulley flange).

To align fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley along fan shaft.

3.Make angular alignment by loosening motor from mounting plate.

To adjust belt tension (see Fig. 33 and 34):

1.Loosen fan motor mounting plate nuts.

2.Units 090-103Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in.

deflection with 5 to 10 lb of force) and tighten mount- ing nuts (see Fig. 33).

Units 120-151Slide motor mounting plate down- ward to tighten belt tension. (1/2-in. deflection with 5 to 10 lb of force.) Secure motor mounting plate nuts. See Fig. 34.

3.Adjust bolt and nut on mounting plate to secure motor in fixed position.

Realign fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley along fan shaft.

3.Make angular alignment by loosening motor from mounting plate.

MOTOR MOUNTING

PLATE NUTS

Fig. 33 — Typical Belt-Drive Motor Mounting

for Sizes 090-103