Table 7 — CO2 Sensor* Standard Settings
|
|
| VENTILATION | ANALOG | CO2 CONTROL | OPTIONAL | RELAY | |
SETTING | EQUIPMENT | OUTPUT | RATE | RELAY SETPOINT | HYSTERESIS | |||
|
|
| (cfm/Person) | OUTPUT | RANGE (ppm) | (ppm) | (ppm) | |
|
|
|
|
| ||||
1 | Interface with Standard | Proportional | Any | 1000 | 50 | |||
2 | Proportional | Any | 1000 | 50 | ||||
Building Control System | ||||||||
3 | Exponential | Any | 1100 | 50 | ||||
| ||||||||
4 |
| Proportional | 15 | 1100 | 50 | |||
5 | Economizer | Proportional | 20 | 0- 900 | 900 | 50 | ||
6 | Exponential | 15 | 1100 | 50 | ||||
| ||||||||
7 |
| Exponential | 20 | 0- 900 | 900 | 50 | ||
8 | Health & Safety | Proportional | — | 5000 | 500 | |||
9 | Parking/Air Intakes/ Loading Docks | Proportional | — | 700 | 50 |
LEGEND
ppm — Parts Per Million
*Available sensor part numbers are listed in Table 4.
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust
Table 8 shows fan rpm at motor pulley settings and Table 9 shows motor efficiencies. Table 10 shows motor performance. Refer to Fan Performance Tables
To change fan speed:
1.Shut off unit power supply and install lockout tag.
2.Loosen belt by loosening fan motor mounting plate nuts (see Fig. 33 and 34).
3.Loosen movable pulley flange setscrew (see Fig. 35).
4.Screw movable flange toward fixed flange to increase fan speed and away from fixed flange to decrease fan speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Tables 1A and 1B.
5.Set movable flange at nearest flat of pulley hub and tighten setscrew (see Tables 1A and 1B for speed change for each full turn of pulley flange).
To align fan and motor pulleys:
1.Loosen fan pulley setscrews.
2.Slide fan pulley along fan shaft.
3.Make angular alignment by loosening motor from mounting plate.
To adjust belt tension (see Fig. 33 and 34):
1.Loosen fan motor mounting plate nuts.
2.Units
deflection with 5 to 10 lb of force) and tighten mount- ing nuts (see Fig. 33).
Units
3.Adjust bolt and nut on mounting plate to secure motor in fixed position.
Realign fan and motor pulleys:
1.Loosen fan pulley setscrews.
2.Slide fan pulley along fan shaft.
3.Make angular alignment by loosening motor from mounting plate.
MOTOR MOUNTING