MODE OF OPERATION

 

PUSHBUTTONS

 

 

LED INDICATORS

 

 

 

 

Button 1

Button 2

DS1 (Red)

DS2 (Yellow)

DS3 (Green)

DS4 (Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STARTUP MODE

Action

 

 

flash

 

flash

 

flash

 

flash

 

 

 

 

 

 

 

 

 

Note 1

Indicators flash in sequence at .5 sec intervals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN MODE

Names

 

 

HB

ECONO

Y1

Y2

Actions

 

 

flash

flash

steady

steady

 

 

 

 

 

 

 

 

 

 

Note 1 Heartbeat Indicator flashes to indicate proper operation of the control

 

 

 

Note 2

Econo indicator flashes to indicate free cooling being used

 

 

 

 

 

Note 3

Y1 and Y2 are on steady when a call thermostat Y1 and Y2 are closed

 

 

 

Note 4

ERROR - HB and Econo are on steady to indicate the presence of an error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

READ

ADV

SET NO

I/O NO

TEN'S

ONES OR

READ MODE

OR ON

OFF

 

 

 

 

 

 

 

 

 

Actions

Push

Push

flash, no

flash no

flash no

flash no

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and release the READ button to enter Read Mode. The SET NO Indicator flashes once to indicate the setup point is selected for viewing

Note 2 Push and release ADV button repeatedly to advance to the desired setup point or I/O point Each time the ADV button is pushed, the SET NO flashes the point number until the desired I/O point is reached and then the I/O NO flashes the I/O point no.

Note 3 After the SET NO indicator identifies the desired point no, push and release the READ button to display the value in the TEN's and ONE's indicator (i.e., 5 flashes for a value of 5) or a steady TEN's indicator for an on and a steady ONE's for off.

To aid in counting, values of 5 are flashed in groups of 5 (i.e., 150 = 3 groups of fast 5 flashes) and then follow by balance in slow flashes (i.e., 7 = 5 quick flashes + 2 slow flashes)

Note 4 Setpoint values are displayed first followed by I/O values and then back to Setpoint values Red Set No LED displays Setup item numbers, and Yellow I/O LED displays I/O item no

Note 5 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

MODE OF OPERATION

 

PUSHBUTTONS

 

LED INDICATORS

 

 

 

 

Button 1

 

Button 2

DS1 (Red)

DS2 (Yellow)

 

DS3 (Green)

 

DS4 (Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

ADJUST

 

ADV

SET NO

SETUP

 

TEN'S

 

ONES OR

SETUP MODE

 

 

OR ON

 

OFF

 

 

 

 

 

 

 

 

 

 

Actions

Hold/Push

 

Push

flash, no

steady

 

flash no

 

flash no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and hold the ADJUST button until the SETUP indicator turns on.

 

 

 

Note 2 Push and release ADV button repeatedly to advance to the desired setup point.

 

 

Each time the ADV button is pushed, the SET NO flashes the point number and then displays

 

the current setting

 

 

 

 

 

 

 

 

 

Note 3

Once the current value has been displayed the TENS indicator will turn on steady and while it

 

on use the ADJUST button to enter the value. (i.e., push the button 4 times to enter 4)

 

Then wait for the ONES indicator to turn on and enter the ONES setting

 

 

 

 

Wait for indicator to turn off and then push read/adjust to check the setting

 

Note 4

Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

 

 

 

 

 

 

 

 

 

 

 

 

 

Names

ADJUST

 

MAN

MAN

I/O NO

 

TEN'S

 

ONES OR

 

 

 

 

OR ON

 

OFF

 

MANUAL

 

 

 

 

 

 

 

 

 

Actions

Push

Hold/Push

steady

flash no

 

flash no

 

flash no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 Push and hold the MAN button until the MAN indicator turns on.

Note 2 Push and release MAN button repeatedly to advance to the desired I/O point. Each time the MAN button is pushed, the I/O NO flashes the I/O point number.

Note 3 After the desired I/O No is reached push and release the ADJUST to toggle the output on and off or open and closed

Note 4 Routine exits after 10 min of no activity or push and hold button 1 and 2 for 3 seconds to exit

APPENDIX A — ECONOMI$ER+ LABEL

I/O POINTS

NO

I/O Points

UNITS

 

 

 

1

C1 Output

-

2

C2 Output

-

3

C3 Output

-

4

C4 Output

-

5

Economizer Damper Output

%

6

Supply Air temperature

F

7

Outside Air temperature

F

8

Return Air Temperature

F

9

Indoor Relative Humidity

%

10

Outdoor Relative Humidity

%

11

Indoor Air Quality

PPM

12

Remote Minimum Position

%

13

Y1 Status (next version)

-

14

Y2 Status (next version)

-

15

G Status (next version)

-

16

Occ Status (next version)

-

ALARM CODES

NO DESCRIPTION

1SAT sensor invalid

2RAT Sensor Invalid (only with changeover type 3&5)

3OAT Sensor Invalid

4ORH Sensor invalid (only with changeover type 3&4)

5IRH Sensor invalid (only with changeover type 5)

6IAQ Sensor Invalid (only if IAQ=1)

7Y2 on Y1 off

8Micro Fails E2 test

note 1 Micro Fails RAM test

note 2 Micro Fails ROM test

Note 1 DS1+DS3/DS2+D4 will alternately flash Note 2 DS1+DS2/DS3+D4 will alternately flash