Bryant 580F installation instructions 54, EconoMi$er+ Inputs and Outputs, Start-UpMode Sequence

Models: 580F

1 80
Download 80 pages 29.14 Kb
Page 54
Image 54

Table 32 — EconoMi$er+ Inputs and Outputs

INPUT

NAME

TYPE

USE

INPUT/OUTPUT

CONVERSION

CONVERSION

CONNECTION

PIN NO.

RANGE

RANGE

RESOLUTION

THERMOSTAT INPUTS

 

 

 

 

 

 

 

 

Y1 (Cool/Low Cool)

Y1

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

1

Y2 (Cool 2/High Cool)

Y2

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

2

G (fan)

G

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

3

Occupied/Unoccupied

OCC

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

4,5

POWER

 

 

 

 

 

 

 

 

Power

24V

Input

Standard

18-30 VAC 50/60 Hz

NA

NA

J2

1,2

ECONOMIZER MOTOR

 

 

 

 

 

 

 

 

Control

CNT

2-10 vdc

Standard

2-10 vdc

0-100%

1%

J2

3,4,5

ANALOG INPUTS

 

 

 

 

 

 

 

 

Supply Air Temperature

SAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

1,2

Outside Air Temperature

OAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

3,4

Return Air Temperature

RAT

10 K Thermistor

Option

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

5,6

Indoor Humidity

IRH

4-20 mA,

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

7,8,9

Loop Powered

 

 

 

 

 

 

 

 

Outdoor Humidity

ORH

4-20 mA,

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

10,11,12

Loop Powered

 

 

 

 

 

 

 

 

Indoor CO2

IAQ

4-20 mA,

Option

4-20 mA, 24 vdc

0-200 PPM/10

10 PPM

J3

13,14

Ext Sourced

Remote Minimum

MIN

10K

Option

10K to 100K Ohms

0 to 100%

1%

J3

15,16,17

Position Pot

 

 

 

 

 

 

 

 

RELAY OUTPUTS

 

 

 

 

 

 

 

 

Cooling Stage 1

CP1

Relay

Standard

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

1,3,4

Cooling Stage 2

CP2

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

2,3,4

Power Exhaust 2/

CP3/

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,6

Cooling Stage 3*

EX2

 

 

 

 

 

 

 

Power Exhaust 1/

CP4/

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,7

Cooling Stage 4†

EX1

 

 

 

 

 

 

 

DISPLAY

 

 

 

 

 

 

 

 

Setpoint Switch 1

SP1

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

Setpoint Switch 2

SP2

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

LED 1

DS1

LED Output

Standard

Red

Logic

On/Off

On Board

NA

LED 2

DS2

LED Output

Standard

Yellow

Logic

On/Off

On Board

NA

LED 3

DS3

LED Output

Standard

Green

Logic

On/Off

On Board

NA

LED 4

DS4

LED Output

Standard

Green

Logic

On/Off

On Board

NA

*If there are 3 stages then there can only be 1 stage of power exhaust.

†If there are 4 stages then there will not be power exhaust stages that will be directly controlled.

Table 33 — Start-Up Mode Sequence

TIME

LED 1/DS1 (RED)

LED 2/DS2 (YELLOW)

LED 3/DS3 (GREEN)

LED 4/DS4 (GREEN)

0-1.0 SEC

OFF

OFF

OFF

OFF

1-1.5 SEC

FLASH ½ SEC

OFF

OFF

OFF

1.5-2.0 SEC

OFF

FLASH ½ SEC

OFF

OFF

2.0-2.5 SEC

OFF

OFF

FLASH ½ SEC

OFF

2.5-3.0 SEC

OFF

OFF

OFF

FLASH ½ SEC

LED — Light-Emitting Diode

54

Page 54
Image 54
Bryant 580F installation instructions 54, EconoMi$er+ Inputs and Outputs, Start-UpMode Sequence