B. Alternate Unit Support
When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit with a minimum of three
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a
NOTE: Horizontal units may be installed on a roof curb if required.
II. STEP 2 — FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building structure on verti- cal units. Do not connect ductwork to unit. For horizontal applications,
Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with appli- cable fire codes.
A minimum clearance is not required around ductwork. Cab- inet
These units are designed for a minimum heating operation continuous
To operate at lower return air temperatures, a
comfort may be compromised when these lower air tempera- tures are used with insufficient heating temperature rise.
III.STEP 3 — INSTALL EXTERNAL TRAP FOR CONDEN- SATE DRAIN
The unit’s
When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installa- tion, relocate the
All units must have an external trap for condensate drain- age. Install a trap a minimum of
The center drain plug looks like a star connection, however it can be removed with a 1/2 in. socket drive extension.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 6 for additional information. Operating weight is shown in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 1 and 6. Refer to rigging instructions on unit.
CAUTION: All panels must be in place when rig- ging and lifting.