tens digit and the DS4 LED will then display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at
NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were displayed. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54.
To read the display again, push the READ/ADJUST (#1) but- ton and the sequence will repeat as many times as needed.
To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycle through all the setup channels (Table 34) and then the I/O channels (Table 35) and then back to the first setup channel.
date or serial no
NOTE: The user can only advance forward, not reset to #1 or go backwards. Cycling the EconoMi$er+ power will reset the item number (but not the item value) to item #1.
In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash.
NOTE: To enter another mode, the user first must exit the Read mode.
If no button is pushed in 10 minutes, Read mode will auto- matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While in the Read mode, the controller will continue to operate with normal unit control.
READ/ | ADVANCE | DS1 | DS2 | DS3 DS4 | |
ADJUST | MANUAL | ||||
|
|
| |||
# 1 |
| RED | YELLOW | GREEN | |
# 2 SETPOINT DISPLAY |
|
PUSH BUTTONS
1 | J1 | INPUTS |
| ||||
|
| ||||||
|
|
|
|
| Y1 (cool 1) |
|
|
| Y1 |
|
|
|
| ||
|
|
|
| ||||
|
|
|
|
|
|
|
|
| Y2 |
|
| Y2 (cool 2) | THERMOSTAT | Occupied/unoccupied | |
5 |
|
|
| ||||
| G |
|
|
| G (fan) |
| I/O support dry circuit |
|
|
| |||||
OCC |
|
| OCC |
| contact (min 24 mA I) | ||
|
|
|
| ||||
|
|
|
|
| 24 VAC |
|
|
| 24V |
|
|
|
|
|
POWER |
| ||
ECONOMIZER | |||
SUPPLY | |||
|
| CONTROL | |
24 VAC | 24 VAC | Control |
J2 | 24V | 24V | CNT |
| |
1 | 5 | ||||
|
|
|
Relays rated at 24 VAC 3A | RELAYS | CP1 | |
24 VAC | |||
cooling, 2 stages of power | |||
and traces for 8A. |
| CP2 | |
NOTE: For 1 and 2 stage |
|
| |
exhaust will be used. | OUTPUT | 24 VAC | |
For 3 cooling stages, only 1 |
| ||
| 24 VAC | ||
stage of power exhaust will be |
| ||
used, and for 4 stages no power |
| EX2/CP3 | |
exhaust will be controlled |
| ||
|
| ||
directly by the control. |
| EX1/CP4 |
ANALOG INPUTS
SAT (10k thermistor) | OAT (10k thermistor) | RAT (10k thermistor) | IRH | Vref | ORH | Vref | IAQ | min (10K pot) | Vref |
J3 |
1 | SAT | OAT | RAT | IRH | VRF | ORH | VRF | IAQ | MIN | VRF |
|
|
|
|
|
|
|
|
|
|
J4
C1
C2
24V
24V
24V
C3
C4
17