Table 18 — Fan Performance 580F120,121 — Vertical Discharge Units; High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

726

0.75

656

793

0.94

822

853

1.14

997

910

1.35

1181

962

1.56

1373

3100

746

0.81

713

811

1.01

883

870

1.21

1062

926

1.42

1250

978

1.65

1447

3200

766

0.88

773

829

1.08

947

887

1.29

1131

942

1.51

1323

993

1.74

1524

3300

786

0.95

836

847

1.16

1016

905

1.37

1204

958

1.60

1400

1008

1.83

1604

3400

806

1.03

904

866

1.24

1088

922

1.46

1280

975

1.69

1481

1024

1.92

1689

3500

826

1.11

975

885

1.33

1163

940

1.55

1360

991

1.78

1565

1040

2.03

1778

3600

846

1.20

1050

904

1.42

1243

958

1.65

1444

1008

1.88

1654

1056

2.13

1870

3700

866

1.29

1129

923

1.51

1327

975

1.75

1532

1025

1.99

1746

1073

2.24

1967

3800

886

1.38

1212

942

1.61

1415

994

1.85

1625

1043

2.10

1843

1089

2.36

2068

3900

907

1.48

1299

961

1.72

1507

1012

1.96

1722

1060

2.21

1944

1106

2.48

2173

4000

927

1.58

1391

980

1.83

1603

1030

2.08

1823

1078

2.33

2049

1123

2.60

2283

4100

948

1.69

1487

1000

1.94

1704

1049

2.20

1928

1095

2.46

2159

1140

2.73

2397

4200

968

1.81

1588

1019

2.06

1809

1067

2.32

2038

1113

2.59

2274

1157

2.87

2516

4300

989

1.93

1694

1039

2.19

1920

1086

2.45

2153

1131

2.73

2393

1175

3.01

2640

4400

1009

2.06

1804

1058

2.32

2034

1105

2.59

2272

1149

2.87

2517

1192

3.15

2768

4500

1030

2.19

1919

1078

2.45

2154

1124

2.73

2397

1168

3.01

2646

1210

3.31

2901

4600

1051

2.32

2039

1098

2.60

2279

1143

2.88

2527

1186

3.17

2780

1228

3.46

3040

4700

1071

2.47

2165

1118

2.75

2409

1162

3.03

2661

1205

3.33

2919

1245

3.63

3184

4800

1092

2.62

2295

1138

2.90

2545

1181

3.19

2801

1223

3.49

3064

1264

3.80

3333

4900

1113

2.77

2431

1158

3.06

2685

1201

3.36

2947

1242

3.66

3214

1282

3.97

3487

5000

1134

2.93

2572

1178

3.23

2832

1220

3.53

3097

1261

3.84

3369

1300

4.16

3647

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3000

1012

1.79

1574

1060

2.03

1781

1105

2.28

1997

1148

2.53

2219

1190

2.79

2449

3100

1027

1.88

1651

1073

2.12

1863

1118

2.37

2081

1161

2.63

2308

1202

2.89

2540

3200

1041

1.97

1732

1088

2.22

1947

1132

2.47

2170

1174

2.73

2400

1215

3.00

2636

3300

1056

2.07

1817

1102

2.32

2036

1146

2.58

2262

1188

2.84

2496

1228

3.12

2735

3400

1071

2.17

1905

1116

2.43

2128

1160

2.69

2359

1201

2.96

2595

1241

3.23

2839

3500

1087

2.28

1998

1131

2.53

2225

1174

2.80

2459

1215

3.08

2699

1255

3.36

2946

3600

1102

2.39

2094

1146

2.65

2326

1188

2.92

2563

1229

3.20

2808

1268

3.48

3058

3700

1118

2.50

2195

1162

2.77

2430

1203

3.04

2672

1243

3.33

2920

1282

3.62

3174

3800

1134

2.62

2300

1177

2.89

2539

1218

3.17

2785

1258

3.46

3036

1296

3.75

3295

3900

1150

2.75

2410

1193

3.02

2653

1233

3.31

2902

1273

3.60

3158

1311

3.90

3420

4000

1167

2.88

2524

1208

3.16

2770

1249

3.45

3024

1287

3.74

3284

1325

4.04

3549

4100

1183

3.01

2642

1224

3.30

2893

1264

3.59

3151

1302

3.89

3414

1340

4.20

3683

4200

1200

3.15

2765

1240

3.44

3020

1280

3.74

3282

1318

4.04

3549

1355

4.36

3823

4300

1216

3.30

2893

1257

3.59

3152

1295

3.89

3418

1333

4.20

3690

1370

4.52

3967

4400

1233

3.45

3025

1273

3.75

3289

1311

4.05

3559

1349

4.37

3834

1385

4.69

4116

4500

1250

3.60

3163

1290

3.91

3431

1328

4.22

3705

1364

4.54

3985

4600

1268

3.77

3306

1306

4.08

3578

1344

4.39

3856

1380

4.72

4140

4700

1285

3.94

3454

1323

4.25

3730

1360

4.57

4013

1396

4.90

4300

4800

1303

4.11

3608

1340

4.43

3888

1377

4.76

4175

4900

1320

4.29

3766

1357

4.62

4051

1394

4.95

4342

5000

1338

4.48

3930

1375

4.81

4219

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 830 to 1130 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 5.25.

3.See page 29 for General Fan Performance Notes.

37

Page 37
Image 37
Bryant 580F installation instructions Airflow

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.