Installing the Device

3.3INSTALLING THE DEVICE

The 2E253-49R may be installed on a tabletop, shelf, or in a 19-inch rack. Section 3.3.1 describes a tabletop or shelf installation and Section 3.3.2 describes the rackmount installation.

To prevent possible personal injury and/or damage to the unit, do NOT connect power to the 2E253-49R until instructed to do so.

3.3.1Tabletop or Shelf Installation

The following two subsections provide guidelines for installation on a tabletop or shelf.

Guidelines for Tabletop and Shelf Installations

Tabletop and shelf installations must be within reach of the network cabling and meet the requirements listed below:

The 2E253-49R must be located within seven feet of two grounded power receptacles that meet the power supply requirements listed in Appendix A.

In a shelf installation, the shelf must support 13.5 kg (30 lb) of static weight for each 2E253-49R.

The temperature at the installation site must be maintained between 5°C (41°F) and 40°C (104°F) with fluctuations of less than 10°C (18°F) per hour.

A clearance of 2 inches must be maintained from the left, right, and rear sides of the device to provide adequate ventilation.

Installation

For a tabletop or shelf installation, locate the 2E253-49R within seven feet of its power source and on an unrestricted free surface area as shown in Figure 3-1. Proceed to Section 3.3.3 for power connection instructions.

To ensure proper ventilation and prevent overheating, leave a minimum clearance space

!of 5.1 cm (2.0 in) at the left, right, and rear of the 2E253-49R, as shown in Figure 3-1.

CAUTION

Installation 3-3