Chapter 3: Installation

3.7.2Rackmount Installation

To install the ESX in a 19-inch rack, Cabletron Systems includes an accessory kit containing the rackmount brackets, mounting screws for attaching the rackmount brackets to the ESX chassis, and a strain-relief bracket for cable management. Screws to mount the ESX to the rack rails are provided by the user.

Guidelines for the Rackmount Installation

The installation site must be within reach of the network cabling and meet the requirements listed below:

An appropriate grounded power receptacle must be located within seven feet of the location.

Maintain a temperature of between 5°C (41°F) and 40°C (104°F) at the installation site with fluctuations of less than 10°C per hour.

In order to allow for proper cooling, there must be a two-inch clearance on either side and the back of the unit.

Installation

Rack mounting the ESX involves the following:

Attaching the strain-relief bracket

Rack mounting the ESX (attaching the mounting brackets and fastening the ESX to the rack)

Attaching the Strain-Relief Bracket

Attach the strain-relief bracket to the front of the ESX as follows:

1.Locate the strain-relief bracket and four 8-32 x 3/8-inch pan head screws in the rackmount kit.

Do not use longer screws to attach the strain-relief bracket. Longer screws could contact electrical components and cause personal injury and/or damage the unit.

2.Attach the strain-relief bracket to the bottom of the ESX using the four 8-32 x 3/8-inch pan head screws (Figure 3-10).