SECTION 7. MEASUREMENT PROGRAMMING EXAMPLES

FIGURE 7.16-3. Hook up to AVW1

Program: AVW1 & CR10 USED TO MEASURE 1 GEOKON VIBRATING WIRE SENSOR.

*1 Table 1 Programs

01:

60

Sec. Execution Interval

01:

P4

Excite,Delay,Volt(SE)

01:

1

Rep

02:15 2500 mV fast Range

03:

1

IN Chan

04:1 Excite all reps w/EXchan 1

05:

1

Delay (units .01sec)

06:

2500

mV Excitation

07:

1

Loc [:TEMP ]

08:

 

.001 Mult

09:

0

Offset

02:

P55

Polynomial

01:

1

Rep

02:1 X Loc TEMP

03:

1

F(X) Loc [:TEMP ]

04:-104.78 C0

05:

378.11

C1

06:-611.59 C2

07:

544.27

C3

08:-240.91 C4

09: 43.089 C5

03:P28 Vibrating Wire (SE)

01:

1

Rep

02:

2

IN Chan

03:1 Excite all reps w/EXchan 1

04:

24

Starting Freq. (units=100 Hz)

05:32 End Freq. (units=100 Hz)

06:500 No. of Cycles

07:0 Rep delay (units=.01sec)

08:2 Loc [:PRESSURE ]

09: -34.836 Mult

7-18