Carrier 48TC*D08 appendix Enthalpy

Models: 48TC*D08

1 98
Download 98 pages 26.51 Kb
Page 41
Image 41
Enthalpy

Configure the unit for Thermostat Mode — Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode.

When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER).

Economizer controls —

Outdoor Air Enthalpy Control (PNO HH57AC077) -

The enthalpy control (HH57AC077) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control. See Fig. 50.)

Locate the enthalpy control in the economizer hood. Locate two GRA leads in the factory harness and connect these leads to enthalpy control sensors 2 and 3. See Fig.

49.Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to TR) and BLK (connect to TR1).

Enthalpy

LCTB

ECON

Switch

 

2

GRA

6

3

GRA

7

 

Factory Wiring Harness

 

 

C08218

Fig. 49 - Enthalpy Switch (HH57AC077) Connections

The outdoor enthalpy changeover setpoint is set at the enthalpy controller.

The enthalpy control receives the outdoor air enthalpy from the outdoor air enthalpy sensor and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Differential Enthalpy Control — Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.

Return Air Enthalpy Sensor — Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). See Fig. 50.

ENTHALPY CONTROLLER

RED

 

S (OUTDOOR

 

 

 

 

 

+

AIR

 

 

 

 

BRN

 

 

B C

TR

TR1

BLK

ENTHALPY

A

 

 

SENSOR)

 

D

SO

+

 

RED

 

 

 

 

SR

+

 

 

S (RETURN AIR

 

 

 

 

 

 

+

ENTHALPY

 

 

2

3

 

 

 

SENSOR)

 

 

1

 

GRAY/ORN

 

 

 

 

 

 

 

 

 

LED

 

 

 

 

WIRE HARNESS

 

 

 

 

GRAY/RED

IN UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Remove factory-installed jumper across SR and + before connecting wires from return air sensor.

2.Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.

3.Remove sensor mounted on back of control and locate in outside air- stream.

C06019

Fig. 50 - Outside and Return Air Enthalpy Sensor

Wiring

To wire the return air enthalpy sensor, perform the following:

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.

2.At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.

3.Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.

NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.

The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controller. A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Indoor Air Quality (CO2 sensor) — The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air.

48TC

41

Page 41
Image 41
Carrier 48TC*D08 appendix Enthalpy