Carrier 48TC*D08 appendix APPENDIX II. PHYSICAL DATA cont, Physical Data, Heating, 7.5 - 12.5TONS

Models: 48TC*D08

1 98
Download 98 pages 26.51 Kb
Page 89
Image 89
APPENDIX II. PHYSICAL DATA (cont.)

APPENDIX II. PHYSICAL DATA (cont.)

Physical Data

(Heating)

 

7.5 - 12.5TONS

 

 

 

 

 

 

 

 

 

48TC**08

48TC**12

48TC**14

Gas Connection

 

 

 

 

 

# of Gas Valves

1

1

1

 

Nat. gas supply line press (in. w.g.)/(PSIG)

4--- 13 / 0.18--- 0.47

4--- 13 / 0.18--- 0.47

4--- 13 / 0.18--- 0.47

 

 

LP supply line press (in. w.g.)/(PSIG)

11---13 / 0.40--- 0.47

11---13 / 0.40--- 0.47

11---13 / 0.40--- 0.47

Heat Anticipator Setting (Amps)

 

 

 

 

 

1st stage

0.14

0.14

0.14

 

 

2nd stage

0.14

0.14

0.14

 

 

 

 

 

 

Natural Gas Heat, Liquid Propane Heat

 

 

 

 

 

# of stages / # of burners (total)

1 / 3

2 / 4

2 / 4

 

 

Connection size

1/2” NPT

3/4” NPT

3/4” NPT

 

LOW

 

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

 

 

 

 

Temperature rise (min/max)

20 --- 50

25 --- 65

25 --- 65

 

 

# of stages / # of burners (total)

2 / 4

2 / 5

2 / 5

 

 

 

 

Connection size

3/4” NPT

3/4” NPT

3/4” NPT

 

MED

 

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

 

 

 

 

Temperature rise (min/max)

35 --- 65

30 --- 65

25 --- 65

 

 

# of stages / # of burners (total)

2 / 5

2 / 5

2 / 5

 

 

 

 

Connection Size

3/4” NPT

3/4” NPT

3/4” NPT

 

HIGH

 

Rollout switch opens / Closes

195 / 115

195 / 115

195 / 115

 

 

 

 

Temperature rise (min/max)

45 --- 75

35 --- 70

35 --- 70

 

 

 

 

 

 

 

 

 

 

 

 

48TC

89

Page 89
Image 89
Carrier 48TC*D08 appendix APPENDIX II. PHYSICAL DATA cont, Physical Data, Heating, 7.5 - 12.5TONS