Carrier 48TC*D08 appendix CO2 Sensor Configuration, CO2 Sensor Standard Settings

Models: 48TC*D08

1 98
Download 98 pages 26.51 Kb
Page 64
Image 64
CO2 Sensor Configuration

48TC

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 83 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 83 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 28.)

Use setting 1 or 2 for Carrier equipment. (See Table 28.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

Table 28 – CO2 Sensor Standard Settings

 

 

 

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

CONTROL

RELAY SETPOINT

HYSTERESIS

OUTPUT

RANGE

 

 

 

(cmf/Person)

(ppm)

(ppm)

 

 

 

 

(ppm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Proportional

Any

0--- 10V

0--- 2000

1000

50

 

4--- 20mA

 

 

 

 

 

 

 

 

Interface w/Standard

 

 

 

 

 

 

2

Proportional

Any

2--- 10V

0--- 2000

1000

50

Building Control System

7--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Exponential

Any

0--- 10V

0--- 2000

1100

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Proportional

15

0--- 10V

0--- 1100

1100

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Proportional

20

0--- 10V

0--- 900

900

50

 

4--- 20mA

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

6

Exponential

15

0--- 10V

0--- 1100

1100

50

 

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Exponential

20

0--- 10V

0--- 900

900

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0--- 10V

0--- 9999

5000

500

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0--- 10V

0--- 2000

700

50

Loading Docks

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64

Page 64
Image 64
Carrier 48TC*D08 appendix CO2 Sensor Configuration, CO2 Sensor Standard Settings