48TC
!WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing
Return-Air Filters
Make sure correct filters are installed in unit (see Appendix II - Physical Data). Do not operate unit without
Outdoor-Air Inlet Screens
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or remove compressor hold down bolts.
Internal Wiring
Check all factory and field electrical connections for tightness. Tighten as required.
Refrigerant Service Ports
Each unit system has two 1/4” SAE flare (with check valves) service ports: one on the suction line, and one on the compressor discharge line. Be sure that caps on the ports are tight.
Compressor Rotation
On
1.Connect service gauges to suction and discharge pressure fittings.
2.Energize the compressor.
3.The suction pressure should drop and the discharge pressure should rise, as is normal on any
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
4.Note that the evaporator fan is probably also rotating in the wrong direction.
5.Turn off power to the unit and install lockout tag.
6.Reverse any two of the unit power leads.
7.
The suction and discharge pressure levels should now move to their normal
NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not provide cooling.
Cooling
Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting approximately 5_F (3_C) below room temperature. Both compressors start on closure of contactors.
Check unit charge. Refer to Refrigerant Charge section.
Reset thermostat at a position above room temperature. Both compressors will shut off. Evaporator fan will shut off immediately.
To shut off unit, set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting.
Main Burners
Main burners are factory set and should require no adjustment.
To check ignition of main burners and heating controls, move thermostat setpoint above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, then lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off.
Refer to Table 11 for the correct orifice to use at high altitudes.
Heating
1.Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding.
2.Turn on electrical supply and manual gas valve.
3.Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature.
4.The
5.After a call for heating, the main burners should light within 5 seconds. If the burner does not light, then there is a
6.The
7.The
8.Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate.
70