Carrier 48TC*D08 Indoor/Outdoor Air Quality CO2 Sensor, 33ZCSENCO2 - Typical Wiring Diagram

Models: 48TC*D08

1 98
Download 98 pages 26.51 Kb
Page 42
Image 42
Fig. 51 - Indoor/Outdoor Air Quality (CO2) Sensor

The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 51 for typical CO2 sensor wiring schematic.

48TC

C07134

Fig. 51 - Indoor/Outdoor Air Quality (CO2) Sensor

(33ZCSENCO2) - Typical Wiring Diagram

To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 51. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TB1-11. See Fig. 52.

C09155

Fig. 52 - Indoor CO2 Sensor (33ZCSENCO2)

Connections

Refer to the Rooftop PremierLink Installation, Start-Up, and Configuration Instructions (Form 33CS-58SI), PremierLink Installation, Start-up, and Configuration Instructions, for detailed configuration information

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) — The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 53. The outdoor air CO2 sensor must be located in the economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 53 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor — A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 51. Connect the 4 to 20 mA terminal to 48TC’s terminal TB1-13. Connect the SIG COM terminal to 48TC’s terminal TB1-11. See Fig. 54.

OAQ Sensor/RH Sensor

TB1PL SEN (33ZCSENCO2) - Typical Wiring Diagram13 Fig. 52 - Indoor CO2 Sensor (33ZCSENCO2)Connections J5-2

TB1

COM Fig. 53 - Outdoor Air Quality Sensor Cover11Fig. 54 - Outdoor CO2 Sensor ConnectionsManual background J5-3

24 VAC

C08275

Fig. 54 - Outdoor CO2 Sensor Connections

42

Page 42
Image 42
Carrier 48TC*D08 Indoor/Outdoor Air Quality CO2 Sensor, 33ZCSENCO2 - Typical Wiring Diagram, Indoor CO2 Sensor 33ZCSENCO2