Power Connections

The following warning applies to the Cisco 3825 router only:

Warning This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than:

60 VDC, 20 A. Statement 1005

The following warning applies to the Cisco 3845 router only:

Warning This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than:

60 VDC, 30 A. Statement 1005

Table 2 and Table 3 summarize DC wiring requirements for Cisco 3825 and Cisco 3845 routers.

For a Cisco 3845 router, the safety ground wire connection must be at the same potential as the 0 V (return) connection.

Table 2

DC Wiring Requirements for Cisco 3825 Routers

 

 

 

 

 

 

 

 

 

DC Input1

 

 

Safety Ground

 

Overcurrent

 

DC Input Wire Size

Wire Size

Wire Terminal (Lug)

Protection

24–36 VDC, 12 A, positive or

AWG 14 (2.0 mm2)

AWG 14 (2.0 mm2),

Amp/Tyco No. 32957

20 A

negative, single or dual source

 

minimum

or equivalent

 

 

 

 

 

 

36–60 VDC, 8 A, positive or negative,

 

 

 

 

single or dual source

 

 

 

 

 

 

 

 

 

 

1. The input voltage tolerance limits for DC power are 18 and 72 VDC.

Table 3

DC Wiring Requirements for Cisco 3845 Routers

 

 

 

 

 

 

 

 

 

DC Input1

 

DC Input

Safety Ground

 

Overcurrent

 

Wire Size

Wire Size

Wire Terminal (Lug)

Protection

24–36 V, 19 A, positive or negative,

AWG 12

AWG 12 (3.0 mm2)

Amp/Tyco No. 34852 or

30 A

single or dual source

(3.0 mm2)

minimum

equivalent

 

36–60 V, 13 A, positive or negative,

AWG 12 or 14

AWG 12 (3.0 mm2)

AWG 12: Amp/Tyco

20–30 A

single or dual source

(3.0 or 2.0 mm2)

minimum

No. 34852 or equivalent

 

 

 

 

 

AWG 14: Amp/Tyco

 

 

 

 

 

No. 32957 or equivalent

 

 

 

 

 

 

 

1. The input voltage tolerance limits for DC power are 18 and 72 VDC.