To connect the router to a DC power source, follow these steps:
Step 1 Remove power from the DC circuit. To ensure that power is removed from the DC circuit, locate the circuit breaker for the DC circuit, switch the circuit breaker to the OFF position, and tape the
Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit. Statement 1003
Tip Secure all power cabling when installing this unit to avoid disturbing
Warning When stranded wiring is required, use approved wiring terminations, such as
Step 2 Strip the wires to the appropriate length for the terminals. The length is 3/16 to 1/4 inch (5 to 6 mm) for Amp/Tyco number 32957 terminals and 5/16 to 3/8 inch (8 to 9 mm) for Amp/Tyco number 34852 terminals.
Step 3 Crimp the terminals onto the DC power input and safety ground wires.
Step 4 Remove the plastic covers from the terminal block. Save the covers for reinstallation after you finish wiring.
Step 5 Connect the wires to the terminal block, starting with the safety ground wire. Connect each wire to the appropriate terminal as shown in Figure 12.
Warning The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated. The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire should always be connected first and disconnected last. Statement 239
Warning An exposed wire lead from a
Caution Do not overtorque the terminal block screws. The recommended torque is 10.0 ± 0.5