Cisco IE 3000 Switch Hardware Installation Guide
OL-13017-01
Appendix B Installation In a Hazardous Environment
Verifying Switch Operation
Step 5 Insert the exposed part of the positive wire into the connection la beled V and the exposed part of the
return wire into the connection labeled RT. See Figure B-14. Make sure that you cannot see any wire
lead. Only wire with insulation should extend from the connector.
Warning
An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure
that no exposed portion of the DC-input power source wire extends from the power and relay
connector.
Statement 122
Figure B-14 Inserting Wires in the Power and Relay Connector
Step 6 Use a ratcheting torque flathead screwdriver to torque the power and relay connector captive screws
(above the installed wire leads) to 2 in-lb. See Figure B-15.
Caution Do not over-torque the power and relay connector captive screws. The torque shou ld not exceed 2 in-lb.
1Power source positive connection 2Power source return connection