Cisco Systems OL-16447-01 manual 3-13, Locate the terminal block plug see Figure

Models: OL-16447-01

1 102
Download 102 pages 41.83 Kb
Page 65
Image 65
Step 2 Locate the terminal block plug (see Figure 3-15).

Chapter 3 Installing and Removing AC- and DC-Power-Supply Modules

Power-Supply Module Installation

Step 1 To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit breaker in the OFF position.

Step 2 Locate the terminal block plug (see Figure 3-15).

Figure 3-15 Terminal Block Plug

280941

Step 3 Identify the positive and negative feed positions for the terminal block connection. The wiring sequence is positive to positive and negative to negative for both the A and the B feed wires.

The switch front panel shows the positive and negative positions for both the A and B feed wires. (See Figure 3-16.)

Figure 3-16 Positive and Negative Positions

1

280942

2

1

Positive position

2

Negative position

Step 4 Use an 18-gauge (1 mm) wire-stripping tool to strip each of the four wires coming from the DC-input power source to 0.27 inch (6.6 mm) ± 0.02 inch (0.5 mm). Do not strip more than 0.29 inch (7.4 mm) of insulation from the wire. Stripping more than the recommended amount of wire can leave exposed wire from the terminal block plug after installation.

Figure 3-17 Stripping the DC-Input Power Source Wire

0.25 in. (6.3 mm) ± 0.02 in. (0.5 mm) 3-13Manual background

60531

Step 5 Insert the exposed wire of one of the four DC-input power source wires into the terminal block plug.

Make sure that you cannot see any wire lead. Only wire with insulation should extend from the terminal block.

 

 

Cisco ME 3400E Ethernet Access Switch Hardware Installation Guide

 

 

 

 

 

 

OL-16447-01

 

 

3-13

 

 

 

 

 

Page 65
Image 65
Cisco Systems OL-16447-01 manual 3-13, Locate the terminal block plug see Figure