TROUBLESHOOTING GUIDE
The following pages contain troubleshooting information intended to aid an experienced service person in diagnosing operational problems that may occur. For further assistance, contact the IMI Cornelius Technical Services department at
PROBLEM
Totally Inoperative
No cooling
No water dispensed, concentrate only
PROBABLE CAUSE
•No power to dispenser due to tripped circuit breaker
•Loose or broken power supply connection inside dispenser.
•Line voltage is not within +/- 10% of nameplate specifications causing compressor overload to trip
•No water in water ice bath or water level extremely low exposing the ice bank sensing probe
•Defective Ice Bank Control or sensing probe
•Cabinet fan is inoperative result- ing in warm concentrate (water continues to cool)
•Compressor short cycles on overload
•Compressor starts but hums and trips overload
•Defective compressor overload or start capacitor
•Compressor starts but does not switch off of start winding
•Refrigerant leak
•No water to dispenser
•Water supply line inside refriger- ated cabinet disconnected from pump platform
•Water solenoid located on pump platform clogged or defective
•Main water solenoid/strainer located at the rear of dispenser is clogged, binding or defective
•Water supply pressure is greater than 80 psi (5.5 bar) forc- ing the brix flow control closed
REMEDY
•Reset circuit breaker. Confirm that breaker is correct size and no other equipment is operating on the same circuit. Also confirm that supply volt- age is +/- 10% of nameplate specifi- cations.
•Repair connection.
•Contact an electrician
•Fill ice bath to proper water level
•Replace
•Replace
•Excessively high discharge pres- sure due to restricted condenser or inoperative condenser fan motor
•Seized or shorted compressor, replace
•Test and replace
•Relay or compressor is defective. Test and replace faulty item
•Repair leak, evacuate and recharge system
•Restore Water
•Reconnect
•Disassemble and clean solenoid. Replace if necessary.
•Remove and clean strainer. Con- firm 28VDC is present at solenoid during dispense. Confirm solenoid coil is not open. Disassemble and clean solenoid.
•Add external regulator and lower pressure to 50 psi (3.5 bar)