Quest Juice Training Manual
PROBLEM
No water and no con- centrate, refrigeration is working
No concentrate dis- pensed, water only
Warm Drink
Water continuously drips from nozzle when in OFF mode
Concentrate warm, water cold
Publication Number: TP00968
| PROBABLE CAUSE |
| REMEDY |
• | • Unplug dispenser and allow | ||
bath | hours to thaw. Check operation of | ||
|
| agitator motor and ice bank control. | |
• |
| • Refrigeration system may be low | |
|
| on charge resulting in a deformed ice | |
|
| bank and | |
|
| in the ice bath. | |
• Black service switch located on | • | Turn on switch | |
the rear of the cabinet door in OFF |
|
| |
position |
|
| |
• White door switch open | • Door switch must be closed in | ||
|
| order to dispense. Check switch | |
|
| operation and replace if necessary. | |
• 6.25 amp fuse inside front elec- | • Replace with 6.25, 250VAC slow | ||
trical box blown | blow fuse and test | ||
• No output from Transformer | • Confirm transformer output by of | ||
|
| 26VAC +/- 2. Replace transformer if | |
|
| necessary. | |
• | Defective voltage regulator | • Measure across the VDC output of | |
board (VRB) located inside front | the board. There should be 28VDC | ||
electrical box | present when the dispense button is | ||
|
| pressed. Replaced VRB if necessary. | |
• Defective dispense push button | • Test and replace if necessary | ||
or portion control board |
|
| |
• Concentrate container not fully | • Refer to Concentrate Loading sec- | ||
engaged into receptacle on pump | tion of this manual | ||
platform |
|
| |
• Dispense/Flush lever in FLUSH | • Move lever to DISPENSE position | ||
position |
|
| |
• Concentrate too cold, not properly | • Concentrate should be | ||
| thawed |
| |
• | Defective pump motor | • | Replace pump motor |
• Ambient air around dispenser is | • | Relocate dispenser | |
| too warm |
|
|
• Excessive demand on dispenser | • Add water | ||
|
|
| penser |
• | Dirty condenser coil | • | Clean condenser coil |
• | Inoperative condenser fan | • Replace condenser fan motor | |
• Defective Ice Bank Control | • Test and replace if necessary | ||
• Loss of refrigerant charge due to | • Repair leak and recharge system | ||
| leak in system |
|
|
• Main water solenoid at base of | • Clean solenoid(s), replace parts as | ||
| unit or water solenoid on pump |
| necessary (refer to the Planned |
| platform not shutting off tightly |
| Maintenance Section) |
• | Cabinet fan inoperable | • | Check/replace fan |
• | Agitator motor/pump inoperable | • | Check/replace agitator motor |
| or restricted |
|
|
• Loss of refrigerant charge due to | • Repair leak and recharge system | ||
| leak in system |
|
|
|
|
|
|
| - 36 - |
| © 2004, IMI Cornelius Inc. |