Storage

5% to 95% RH with 33 °C (91 °F) maximum dew point.

 

Atmosphere must be non-condensing at all times.

Maximum Vibration

 

Operating

0.26 Grms at 5 Hz to 350 Hz (all operation orientations).

Storage

1.87 Grms at 10 Hz to 500 Hz for 15 min (all six sides

 

tested).

Maximum Shock

 

Operating

One shock pulse in the positive z axis of 31 G for 2.6 ms in

 

all operational orientations.

Storage

Six consecutively executed shock pulses in the positive

 

and negative x, y, and z axes (one pulse on each side of

 

the system) of 71 G for up to 2 ms.

Maximum Altitude

 

Operating

3048 m (10,000 ft).

Storage

12,000 m (39,370 ft).

Operating Altitude De-rating

 

35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300 m (1 °F/547

 

ft) above 950 m (3,117 ft).

40 °C (104 °F)

Maximum temperature is reduced by 1 °C/175 m (1 °F/319

 

ft) above 950 m (3,117 ft).

45 °C (113 °F)

Maximum temperature is reduced by 1 °C/125 m (1 °F/228

 

ft) above 950 m (3,117 ft).

Particulate Contamination

 

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.

Air Filtration

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Conductive Dust

NOTE: Applies to data center and non-data center environments.

Corrosive Dust

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

Air must be free of corrosive dust.

67