VENTING INSTALLATION INSTRUCTIONS

13

Installation Planning (Cont.)

HORIZONTAL SYSTEM INSTALLATION USING TWO 90°

ELBOWS

The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

Venting with Two 90° Elbows

 

Horizontal (H1) +

90° Elbow

Vertical (V)

 

Horizontal (H2)

 

8' min.

9' max.

 

9' min.

11' max.

 

10' min.

13' max.

 

12' min.

17' max.

 

14' min.

20' max.

 

Figure 24 - Horizontal Termination Configuration for Venting using Two 90° Elbows (Model (V)CD36T)

Venting with Three 90° Elbows

 

Vertical (V)

 

Horizontal (H1) +

 

Horizontal (H1)

Horizontal (H2)

90° Elbow

5' min.

2' max.

6' max.

 

6' min.

3' max.

8' max.

 

7' min.

4' max.

10' max.

 

8' min.

5' max.

12' max.

 

12' min.

8' max.

20' max.

 

20' max.

8' max.

20' max.

 

Figure 25 - Horizontal Termination Configuration for Venting using Three 90° Elbows (Model (V)CD36T)

116035-01B

www.desatech.com

Page 13
Image 13
Desa (V) CD36R(N, (V) CD36T(N, P) installation manual Venting with Two 90 Elbows, Venting with Three 90 Elbows