LOCATION OF TERMINATION CAP

7

LOCATION OF TERMINATION CAP

N N

D

 

 

 

 

H

E

 

 

 

 

 

V

 

 

 

 

 

B

C

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

Fixed

V Openable

B

V

 

Closed

Fixed

 

 

Openable

 

 

Closed

 

F

 

 

 

B

V

 

 

 

 

 

B

V

J X

G

 

B

 

 

 

 

 

A

 

 

 

 

 

 

 

I

M V

K X

G V

G V A

V TERMINATION CAP

X AIR SUPPLY INLET

G GAS METER

RESTRICTED AREA (TERMINATION PROHIBITED)

A = clearance above grade, veranda, porch, deck, or balcony [*12 inches (30.5mc) minimum]

B = clearance to window or door that may be opened [12 inches (30.5cm) minimum]

C = clearance to permanently closed window [minimum 12 inches (30.5cm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (61cm) from the center-line of the terminal [18 inches (45.7cm) minimum]

E= clearance to unventilated soffit [12 inches (30.5cm) minimum] F = clearance to outside corner (see below)

G = clearance to inside corner (see below)

H = *not to be installed above a meter/regulator assembly within

36 inches (91.4cm) horizontally from the center-line of the regulator

I = clearance to service regulator vent outlet [*72 inches (182.9cm) minimum]

J= clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [*12 inches (30.5cm)

minimum]

K= clearance to a mechanical air supply inlet [*72 inches (182.9cm) minimum]

L= clearance above paved side-walk or a paved driveway located on public property [*84 inches (213.3cm) minimum]

M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ]

N= clearance above a roof shall extend a minimum of 24 inches (61cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)

vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings*

only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*

*as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances

����������������������������������������������������������������������������������

���������������������������

�����������������

A

A = 6" (15.2cm)

V

V

B B = 6" (15.2cm)

 

D

C

C

E

V

�������������������������������������������������������������

 

H

G

V

 

V

J

 

Combustible &

Noncombustible

G = 12" (30.5cm) minimum clearance H = 24" (61cm)

J = 20" (50.8cm)

C = Maximum depth of 48" (121.9cm) for recessed location

D = Minimum width for back wall of recessed location - Combustible - 38" (965mm) Noncombustible - 24" (61cm)

E = Clearance from corner in recessed location- Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)

Figure 10 - Minimum Clearances for Termination Cap

116035-01B

www.desatech.com

Page 7
Image 7
Desa (V) CD36R(N, (V) CD36T(N, P) installation manual Location of Termination CAP, Minimum Clearances for Termination Cap