GAS SUIPPLY AND PIPING (Cont.)

23

Checking Gas Connections

GAS SUPPLY AND PIPING Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing. or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak.Applynoncorrosiveleakdetectionfluidtoalljoints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve fromthegassupplypipingsystem.Pressuresinexcessof1/2psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or by using compressed air.

4.Check all joints of gas supply piping sytem. Apply noncorro- sive leak detection fluid to all joints at once.

5.Reconnect fireplace and equipment shutoff valve to gas supply Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 50).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or by using compressed air.

4.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 51 for propane/LP or Figure 52 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

EquipmentOpen

Shutoff

Valve

Closed

Propane/LP

Equipment

Supply Tank

Shutoff

 

Valve

Gas Valve

Figure 51 - Checking Gas Joints for Propane/LP Gas Fireplace

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve

Figure 52 - Checking Gas Joints for Natural Gas Fireplace

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Figure 50).

2.Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace.

3.Check all joints from equipment shutoff valve to gas valve (see Figure 51 for propane/LP or Figure 52 for natural gas, Apply noncorrosive leak detection fluid to all joints. Bubbles formed show a leak. Correct all leaks at once.

5.Light fireplace (see Operating Fireplace, page 25 or 27 depend- ing on ignition system). Check all other internal joints for leaks.

5.Turn off fireplace (see To Turn Off Gas toAppliance, page 26 or page 27 depending on ignition system).