VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

VENTING INSTALLATION

INSTRUCTIONS

Continued

GROUND FLOOR INSTALLATION TOP VENT

Recommended Applications for Top Vent Model (V)CD36T:

Installation using cabinet surrounds

Through the wall using round or square termination (up to a maximum of 24” of horizontal pipe)

Corner installation

(Using one 90° elbow and a maximum of 24” of horizontal pipe).

Horizontal

Straight / Adjustable

Square

Pipe 24" Max.

Required

Vertical (V)

Allowable

Vertical (V)

Vertical Pipe

Horizontal (H)

45 ½”

None

26” Max.

57 ¼” Min.

1 ft.

30” Max.

69 ¼” Min.

2 ft.

74” Max.

81 ½” Min.

3 ft.

98” Max.

94” Min.

4 ft.

122” Max.

106” Min.

5 ft.

146” Max.

159” Min.

9 ft.

20’ Max.

Termination

 

 

90°

 

Wall

Elbow

 

 

V

Firestop

 

H

Corner Installation Vertical (V) Horizontal (H)

45 ½“

32 ½“

Square Termination

Not to Exceed

(H) Limits

90° Elbow

As Required for (V)

See Chart for Pipe

Section Required

Wall

Firestop

Figure 21 - Horizontal Termination Configuration for Corner Installation using One 90° Elbow (Model (V)CD36T)

Figure 22 - Horizontal Termination Configuration with Vertical Rise and One 90° Elbow (Model (V)CD36T)

SNORKEL TERMINATION INSTALLATION

Recommended Applications Models (V)CD36R and (V)CD36T:

Installations requiring vertical rise on building exterior.

Installation using snorkel termination to achieve 1 ft. above grade.

Snorkel terminati

you must provide proper drainage to prevent water from entering snorkel (see Figure 23). Do not back fill around snorkel termination.

Snorkel Termination

12"

Minimum

Snorkel

Termination Wall

90° Elbow Firestop

12"

Minimum

Adequate

Drainage

Snorkel Termination

12"

Minimum

Figure 23 - Snorkel Termination Configurations for Below Ground Installation