RG=1 means that

new sample shall be taken once per time quantum. If TS=60, and

RP[0]=0, the recorder will sample once per 240usec.

 

RG=2 means that

new sample shall be taken once per two time quanta. If TS=60, and

RP[0]=1, the recorder will sample once per 120usec.

 

Similarly, RG=N means that a new sample shall be taken once per N time quanta. Note that RG specifies only the recorder sampling-rate, not the trigger sampling-rate. A trigger event will cause the recorder to start within one time quantum.

RL defines the number of maximal data items to collect.

For example, if RL=11, TS=60,RG=1, RP[0]=0, then the 11 samples at the rate of 240usec shall be taken, lasting (111) × 240u sec = 2400usec.

The recorder has a limited memory – total of 8kb. When more signals are recorded, less memory is available for each recorded signal.

If RL > (recorder memory) /(number of signals) , the recorder will fail to record the specified RL samples – instead it will record to fill its data volume.

The actual amount of recorded data can be polled using WI[21].

8.5 Trigger events and timing

The recorder is started by a trigger event.

The trigger event may be one of the following:

Immediate: The recorder starts immediately after the recording request has been issued.

Motion begin: The recorder is triggered by the execution of a software BG command, or by timed BG command, or by a hardware commanded hardware

begin.

Triggered by an analog signal: The recorder starts upon the following event: o Positive slope – The signal crosses a prescribed level with positive

slope

o Negative slope – The signal crosses a prescribed level with negative slope

o Window – The signals exits a window of two prescribed signal levels.

The picture below depicts the positive slope, negative slope, and window trigger types.

1

 

 

0.8

Trigger signal (not necessarily

 

 

0.6

 

Level 1

 

 

0.4

The trigger

 

 

The trigger

0.2

occur here if set

occur here if set

 

for negative slope

for positive slope

 

 

0

 

 

 

The trigger

 

 

 

-0.2

 

 

occur here if set

 

 

 

 

for window

 

 

 

 

 

 

 

 

 

-0.4

 

 

Level 2

 

 

 

 

 

 

 

 

 

-0.6

 

 

 

 

 

 

-0.8

 

 

 

 

 

 

-1

2

3

4

5

6

7

1

97

Page 99
Image 99
Elmo HARSFEN0602, HARmonica software manual Trigger events and timing