Specifications 15

 

 

Table 4 - Ambient conditions for the rectifier

 

 

 

 

 

 

 

Operating

A minimum airflow clearance of 2 inches ( 5 cm ) is

 

 

conditions

required at the rear of the rectifier.

 

 

 

The rectifier will operate properly under the following

 

 

 

conditions.

 

 

 

 

 

Temperature:

32°F to 122°F

( 0°C to +50°C )

 

 

 

 

32°F to 104°F

( 0°C to +40°C ) with air

 

 

 

 

filters

 

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at 4

 

 

 

 

kPa max. equiv. to 7,000 ft. ( 2,100 m )

 

 

 

 

above sea level

 

 

Transportation

During transportation, the rectifier can be subjected to

 

 

conditions

the following conditions without sustaining damage.

 

 

 

Temperature:

–67°F ( –55°C ) for 16 hours

 

 

 

 

140°F ( +60°C ) dry heat

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at

 

 

 

 

4 kPa max.

 

 

 

 

Vibration:

38 mm / s max. ( 10 Hz to 30 Hz )

 

 

 

 

sinusoidal, 18-inch ( 457 mm ) drop

 

 

 

 

when packaged

 

 

 

Pressure:

12 kPa min. equiv. to 49,212 ft.

 

 

 

 

( 15,000 m above sea level)

 

 

 

Temperature shock : − 58°F to 140°F ( − 50°C to 60°C )

 

 

Storage conditions

During storage, the rectifier may be subjected to the

 

 

 

following conditions without damage :

 

 

 

Temperature:

–67°F ( –55°C ) for 16 hours to 140°F

 

 

 

 

( +60°C ) dry heat

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at

 

 

 

 

4 kPa maximum

 

 

 

The rectifier contains aluminum electrolytic capacitors

 

 

 

that have a shelf life of five years or greater at the

 

 

 

maximum rated storage temperature.

 