14 Specifications

2.2.Operation specifications and ambient conditions

Table 3 - Operation specifications of the rectifier

Output regulation :

At the output terminals, the voltage is within ±0.5% of

 

the set voltage value for all specified input and output

 

variations, and within ±1% for any combination of

 

specified input, output and ambient conditions.

Temperature drift :

Unless otherwise stated, all input and output

 

parameters such as input voltage range, output current

 

and voltage, current limit, etc. shall not vary more than

 

2% over the operating temperature range.

Output noise and

• less than 22 dB of random noise on C band at voice

ripple :

frequency over the entire operating range of the

 

rectifier, including operation in the current limit mode,

 

and at low, nominal and high input voltage conditions

 

( with or without batteries and measured at the point

 

of regulation )

 

• less than 20 mV RMS in any 3 kHz band between 10

 

kHz and 20 MHz ( measurements made with or

 

without batteries at the output terminals of the

 

rectifier and with the rectifier in the local sensing

 

mode )

 

• less than 250 mV peak to peak switching voltage

 

spikes ( measured differentially with an a 100 MHz

 

oscilloscope )

Total harmonic

Less than 5%.

distortion ( THD ) :

 

Efficiency :

Better than 89% at a nominal input voltage of 350 V ac

 

and for an output current ( load ) greater than 80 A.

Power factor :

Better than 99% with an output current ( load ) greater

 

than 80 A.

Heat dissipation :

The maximum heat dissipation is 1420 watts

 

( 4846 BTU / hr ) for an output current ( load ) of 200 A

 

at –58 V dc ( when the ac input is 330-475 V )

Electromagnetic

The NT5C05CA / CB rectifiers when used in the

interference ( EMI ) :

rectifier cabinet NT6C43CA / CB ( equipped with the

 

ac EMI filter kit NT6C18KB, or the NT5C05CC without

 

external EMI filter ) meet the CISPR requirements for

 

conducted and radiated EMI as specified in Publication

 

22 for Class "A" equipment.

Reliability:

The rectifier has an MTBF greater than 120 000 hours

 

under normal operating conditions, at 77°F ( 25°C ) as

 

per Telcordia Technologies TR332 method.

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Page 14
Image 14
Emerson 200I/48-NT5C05C user manual Operation specifications and ambient conditions