36 Functional description

Table 11 - Adjusting the potentiometers and switches

Potentiometers

Description

CL ADJ

Current limit adjust ( 100 A to 210 A )

CUR CAL

Current reading calibration

EQL ADJ

Equalize voltage adjust ( 0 V to − 4 V )

FLT ADJ

Float voltage adjust ( − 46 V to − 58 V )

HVSD ADJ

High voltage shutdown adjust ( − 52 V to − 60 V )

VOLT CAL

Voltage reading calibration

Switches

Description

EQL / FLT

Equalize / Float selection switch

SLS / FS

Slope load sharing / Forced load sharing selection

ST UP DELAY

Start-up delay selection DIP ( 4 sec to 2 min )

VOLT / AMP

Voltage and current display selection switch

Table 12 - Rectifier input / output signals to the controller

 

 

Designation

Description

RG+ / RC−

External reference voltage across the batteries

 

measured through the controller to regulate the voltage.

HVSD

Remote High Voltage Shutdown input activated by a

 

BAT RTN signal.

HVSDR

Remote High Voltage Shutdown Reset input activated by

 

a BAT RTN signal.

TR

Remote Inhibit input activated by a BAT RTN signal.

EQL

Remote Equalize input activated by a BAT RTN signal.

RFA

Rectifier Failure Alarm output activating a form C contact

F ALM

Fan Failure Alarm output activating a form C contact

SHUNT ( + ) and

Rectifier Current input / output ( 50 mV / 250 A )

SHUNT ( − )

 

CURRENT

Common Forced Current Share Mode ( 0-12 V )

SHARE

 

4.2.5.Voltage / current displaytest and measurement

CUR CAL / VOLT CAL potentiometers

These potentiometers are used to calibrate the digital display meter for current and voltage measurements. As the two potentiometers affect each other, current calibration must be performed before voltage calibration.