16 Specifications

2.3.Mechanical and electrical specifications of a 1200 A cabinet

Table 5 - Mechanical specifications of the NT6C43CB 1200 A cabinet

Height :84.00 inches ( 213.36 cm )

Depth :

23.63 inches ( 60.0 cm )

 

 

Width :

23.63 inches ( 60.0 cm )

Table 6 - Electrical specifications of the NT6C43CB 1200 A cabinet

Input voltage :

380 / 415 V ac three phase

Output voltage :

–46 V dc to –58 V dc

Output current :

1200 A

2.4.Ambient conditions of a 1200 A cabinet

Table 7 — Ambient conditions for the NT6C43CB 1200 A cabinet

Operating

The cabinet is designed for use under the following

conditions

ambient conditions.

 

Temperature:

0°C to 50°C ( 32°F to 122°F )

 

 

0° to 40°C ( 32° to 104°F ) with air

 

 

filters

 

Humidity:

0 to 95% RH ( non-condensing )

 

Altitude:

sea level to 7,000 ft ( 2,100 m )

Storage conditions

During transportation and storage, the acceptable

 

ambient conditions are :

 

Temperature: –55°C ( –67°F )

 

 

+60°C ( 140°F ) dry heat

 

Humidity:

0 to 95% RH ( non-condensing )

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Page 16
Image 16