42 Functional description
Remote ON / OFF control TR
When a ground signal is applied to the 'Temporary Release' ( TR ) input, the rectifier inhibits its operation and triggers the RFA. When the remote ground signal is discontinued the rectifier returns to normal operation ( see Table 14 ).
Start up delay DIP switch
The rectifier can provide a
120 seconds, with a resolution of 8 seconds and an accuracy of +1 second. Use of this feature is recommended when two or more rectifiers are connected to a common ac input to stagger the inrush currents. A front panel DIP switch can be set to provide the
4.2.11.Control signals on connector P1
The P1 connector, located at the rear of the rectifier, can be used to verify all the control and alarm signals when troubleshooting the rectifier ( see Table 14 ).
The control inputs are activated by a ground ( BAT RTN ) signal. The alarms, extended by relay contacts, are isolated from each other and the rectifier frame. All contacts are rated 60 V and 0.5 A dc. The normal status of each contact is defined when the rectifier operates normally in the remote sense mode with no alarm. Contacts NC ( normally closed ) and NO ( normally opened ) refer to the
Table 14 - Control signal connections on P1
Connection | Signal |
| Description |
EQL |
| Equalize | |
RC − |
| Remote sense ( − ) | |
|
|
|
|
HVSDR |
| High voltage shutdown reset | |
RFA ( NC ) |
| Rectifier fail alarm ( NC ) | |
FAN ALM ( NC ) |
| Fan fail alarm ( NC contact ) | |
FAN ALM ( C ) |
| Fan fail alarm ( C ) | |
SH− |
| Output current shunt voltage ( - ) | |
RFA ( NO ) |
| Rectifier fail alarm ( NO ) | |
SENSE ( C ) |
| Sense fail alarm ( C ) | |
SENSE ( NO ) |
| Sense fail alarm ( NO ) | |
| | continued |
UM5C05C P0745680 Standard 6.00 October 2001 | Emerson Energy Systems |