22 Installation
Procedure 2 - Installing a rectifier in a cabinet ( continued )
Step | Action |
4 | Place the rectifier on the |
| position of the cabinet and slide it towards the rear until the mounting |
| brackets come into contact with the frame of the cabinet. The front of |
| the rectifier should be flush with the front of the cabinet and the |
| output bussing should be in contact with the riser busbars located at |
| the rear of the cabinet. |
5 | Align the mounting holes in the brackets of the rectifier with the |
| mounting holes in the frame. Secure the rectifier in place by inserting |
| and tightening the |
| Note : Install an external tooth lock washer on one of the screws to |
| assure good ground continuity between the rectifier and the |
| frame. |
| end |
Figure 4 - Installing the rectifier
HELIOS
| VOLT |
|
|
| VOLT |
|
|
|
|
|
| CAL |
|
| AMP |
|
|
| CUR | CL |
|
|
|
| CAL | ADJ | |
|
|
| VOLT/AMP |
|
| EQL |
|
|
|
|
|
| ADJ |
|
|
|
|
|
| EQL |
| THSD | RFA | SEN | AC ON |
| FLT |
AC/CA | HVSD | ALM | FAIL | CL | FF1 | FF2 |
EQL | 1.0A | FLT | ||||
|
| FAN |
|
| 1.0A | |
|
| VOUT+ | VOUT- |
|
| ADJ |
|
|
|
|
|
| HVSD |
|
|
|
|
|
| ADJ |
|
|
|
|
|
| ST UP |
|
|
|
|
|
| DLY |
|
|
|
|
|
| SLS FS |
|
|
|
|
| DC/CC |
|
HELIOS
VOLT
CAL
3.4.Cabling and connecting
ET LOCK WASHER
The ac cables of the rectifier must always exit each rectifier from the right side, when viewed from the rear.
The dc cables of the rectifier must always exit each rectifier from the left side, when viewed from the rear.
The system alarm interface cable must always exit each rectifier from the right side, when viewed from the front.
UM5C05C P0745680 Standard 6.00 October 2001 | Emerson Energy Systems |