22 Installation

Procedure 2 - Installing a rectifier in a cabinet ( continued )

Step

Action

4

Place the rectifier on the L-shaped guides located in the lowest

 

position of the cabinet and slide it towards the rear until the mounting

 

brackets come into contact with the frame of the cabinet. The front of

 

the rectifier should be flush with the front of the cabinet and the

 

output bussing should be in contact with the riser busbars located at

 

the rear of the cabinet.

5

Align the mounting holes in the brackets of the rectifier with the

 

mounting holes in the frame. Secure the rectifier in place by inserting

 

and tightening the self-tapping screws removed in Step 3.

 

Note : Install an external tooth lock washer on one of the screws to

 

assure good ground continuity between the rectifier and the

 

frame.

 

end

Figure 4 - Installing the rectifier

HELIOS

 

VOLT

 

 

 

VOLT

 

 

 

 

 

 

CAL

 

 

AMP

 

 

 

CUR

CL

 

 

 

 

CAL

ADJ

 

 

 

VOLT/AMP

 

 

EQL

 

 

 

 

 

 

ADJ

 

 

 

 

 

 

EQL

 

THSD

RFA

SEN

AC ON

 

FLT

AC/CA

HVSD

ALM

FAIL

CL

FF1

FF2

EQL

1.0A

FLT

 

 

FAN

 

 

1.0A

 

 

VOUT+

VOUT-

 

 

ADJ

 

 

 

 

 

 

HVSD

 

 

 

 

 

 

ADJ

 

 

 

 

 

 

ST UP

 

 

 

 

 

 

DLY

 

 

 

 

 

 

SLS FS

 

 

 

 

 

DC/CC

 

HELIOS

VOLT

CAL

3.4.Cabling and connecting

SELF-TAPPING SCREW ( P097F813 )

ET LOCK WASHER

The ac cables of the rectifier must always exit each rectifier from the right side, when viewed from the rear.

The dc cables of the rectifier must always exit each rectifier from the left side, when viewed from the rear.

The system alarm interface cable must always exit each rectifier from the right side, when viewed from the front.

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Page 22
Image 22
Emerson 200I/48-NT5C05C user manual Cabling and connecting, Installing the rectifier