20 Installation
DANGER
Short circuit hazard
The rectifiers, and the batteries in particular, can deliver high current if a short to ground occurs. When working on live equipment, remove all personal jewellery, use properly insulated tools, and cover any live busbars with a insulating sheet of canvas to prevent short circuits that could be caused by falling tools or parts.
3.3.1.Installing in a frame
When shipped, the NT5C05CA / CB / CC switch mode rectifiers are configured for installation in a standard frame. As the rectifier is heavy, use a manual forklift to mount the rectifier in a frame. If a forklift is not available, two persons, exercising care, can lift the rectifier into place and secure it.
Procedure 1 - Installing the rectifier in a frame
Step | Action |
1 | Note : Install each rectifier beginning with the lowest mounting |
| position in the frame. |
| Align the mounting brackets of the rectifier with the mounting holes in |
| the frame and insert the locating pins into these holes. |
2 | Lift the rectifier and align the middle holes in the mounting brackets |
| of the rectifier with the locating pins inserted in the frame. Slide the |
| rectifier into position onto the locating pins. |
3 | Secure the rectifier to the frame by inserting and tightening a |
| mounting screw ( provided ) in the uppermost holes of each |
| mounting bracket ( one on the left side and one on the right side ). |
4 | Remove the locating pins and install the other six mounting screws. |
| Tighten the screws applying a torque of 6.5 ± 0.5 |
| 0.5 |
| end |
3.3.2.Installing in a cabinet
The cabinet is 23.56 inches ( 600 mm ) wide and deep, and 84 inches
( 2134 mm ) high. The anchors provided to secure the cabinet in place are intended for installation on 3000 psi ( 2 kg per sq. mm ) compressive strength concrete. Anchors for seismic applications are available upon request. Slotted holes are provided in the base of the cabinet for anchoring. The primary locations should be used as a first choice ( see Figure 3 ). If a
UM5C05C P0745680 Standard 6.00 October 2001 | Emerson Energy Systems |