20 Installation

DANGER

Short circuit hazard

The rectifiers, and the batteries in particular, can deliver high current if a short to ground occurs. When working on live equipment, remove all personal jewellery, use properly insulated tools, and cover any live busbars with a insulating sheet of canvas to prevent short circuits that could be caused by falling tools or parts.

3.3.1.Installing in a frame

When shipped, the NT5C05CA / CB / CC switch mode rectifiers are configured for installation in a standard frame. As the rectifier is heavy, use a manual forklift to mount the rectifier in a frame. If a forklift is not available, two persons, exercising care, can lift the rectifier into place and secure it.

Procedure 1 - Installing the rectifier in a frame

Step

Action

1

Note : Install each rectifier beginning with the lowest mounting

 

position in the frame.

 

Align the mounting brackets of the rectifier with the mounting holes in

 

the frame and insert the locating pins into these holes.

2

Lift the rectifier and align the middle holes in the mounting brackets

 

of the rectifier with the locating pins inserted in the frame. Slide the

 

rectifier into position onto the locating pins.

3

Secure the rectifier to the frame by inserting and tightening a

 

mounting screw ( provided ) in the uppermost holes of each

 

mounting bracket ( one on the left side and one on the right side ).

4

Remove the locating pins and install the other six mounting screws.

 

Tighten the screws applying a torque of 6.5 ± 0.5 ft-lbs ( 8.5 ±

 

0.5 N-m ).

 

end

3.3.2.Installing in a cabinet

The cabinet is 23.56 inches ( 600 mm ) wide and deep, and 84 inches

( 2134 mm ) high. The anchors provided to secure the cabinet in place are intended for installation on 3000 psi ( 2 kg per sq. mm ) compressive strength concrete. Anchors for seismic applications are available upon request. Slotted holes are provided in the base of the cabinet for anchoring. The primary locations should be used as a first choice ( see Figure 3 ). If a steel-reinforcing rod is encountered when drilling the holes for the anchors

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Page 20
Image 20
Emerson 200I/48-NT5C05C user manual Installing in a frame, Installing in a cabinet, Short circuit hazard