Installation 23

3.5.Connecting the dc output terminals to the busbars

The dc outputs of the rectifier are connected to the busbars as illustrated in Figure 5. There are two methods :

BAT GRD ( + ) of the rectifier connected to the CHG/ DISCH GRD busbar and the –48 V of the rectifier connected to the CHG BAT busbar

BAT GRD ( + ) of the rectifier connected to the CHG GRD busbar and the -48V of the rectifier connected to the CHG/ DISCH BAT busbar

Figure 5 - Connecting the dc to the busbars with a shunt on the battery side or a shunt on the ground side

+

-

+ BAT GRD

RECTIFIER - -48V

CHG / DISCH GRD BUSBAR

CHG BAT

BUSBAR

LOAD

SHUNT DISCHARGE BAT BUSBAR

FUSE

PANEL

SHUNT ON THE BATTERY SIDE

+

-

+ BAT GRD

RECTIFIER - -48V

CHG GRD

BUSBAR

CHG / DISCH BAT BUSBAR

SHUNT

DISCHARGE

GRD BUSBAR

LOAD

FUSE

PANEL

SHUNT ON THE GRD SIDE ( PREFERRED CONFIGURATION )

Emerson Energy Systems

Rectifier 200I/48NT5C05C Installation and User Manual

Page 23
Image 23
Emerson 200I/48-NT5C05C user manual Connecting the dc output terminals to the busbars